Table 11 Electrical Specifications - Bard WA Series User Manual

Table of Contents

Advertisement

Rated
No. Field
Volts
MODEL
Power
&
Circuits
Phase
W3SAC-A00, A0Z
1
A05
1
A10
1
230/208-1
A15
1 or 2
A20
1 or 2
W3SAC-B00, B0Z
1
B06
1
230/208-3
B09
1
B15
1
W3SAC-C00, C0Z
1
C06
1
460-3
C09
1
C15
1
W4SAC-A00, A0Z
1
A05
1
A10
1
230/208-1
A15
1 or 2
A20
1 or 2
W4SAC-B00, B0Z
1
B06
1
B09
230/208-3
1
B15
1
B18
1
W4SAC-C00, C0Z
1
C09
1
460-3
C15
1
W5SAC-A00, A0Z
1
A05
1
A10
230/208-1
1
A15
1 or 2
A20
1 or 2
W5SAC-B00, B0Z
1
B06
1
B09
1
230/208-3
B15
1
B18
1 or 2
W5SAC-C00, C0Z
1
C09
460-3
1
C15
1
 Maximum size of the time delay fuse or circuit breaker for protection of field wiring conductors.
 Based on 75°C copper wire. All wiring must conform to the National Electrical Code and all local codes.
 These "Minimum Circuit Ampacity" values are to be used for sizing the field power conductors. Refer to the National Electrical code (latest
version), Article 310 for power conductor sizing.
CAUTION: When more than one field power circuit is run through one conduit, the conductors must be derated. Pay special attention
to Note 8 of Table 310 regarding Ampacity Adjustment Factors when more than three current carrying conductors are in a
raceway.
IMPORTANT: While this electrical data is presented as a guide, it is important to electrically connect properly sized fuses and conductor
wires in accordance with the National Electrical Code and all local codes.
Electrical Specifications
Single Circuit
Maximum
Field
Minimum
External
Power
Ground
Circuit
Fuse or
Wire
Wire
Ampacity
Ckt. Brkr.
Size
24
35
8
10
31
40
8
10
57
60
6
10
83
90
4
8
109
125
2
6
18
25
10
10
23
35
8
10
32
35
8
10
50
60
8
10
10
15
14
14
12
15
14
14
17
20
12
12
26
30
10
10
33
50
8
10
33
50
8
10
58
60
6
10
84
90
4
8
110
125
2
6
24
35
8
10
24
35
8
10
33
35
8
10
51
60
6
10
60
60
6
10
12
15
14
14
18
20
12
12
27
30
10
10
38
50
8
10
38
50
8
10
59
60
6
10
85
90
4
8
111
125
2
6
28
40
8
10
28
40
8
10
34
40
8
10
52
60
6
10
61
70
6
8
14
20
12
12
18
30
10
10
26
30
10
10
TABLE 11
 Minimum
 Maximum
Circuit
External Fuse or
Ampacity
Ckt. Breaker
Ckt. A Ckt. B Ckt. C Ckt. A Ckt. B Ckt. C Ckt. A Ckt. B Ckt. C Ckt. A Ckt. B Ckt. C
57
26
60
30
57
52
60
60
59
26
60
30
59
52
60
60
38
52
40
60
59
52
60
60
34
28
40
30
Multiple Circuit
Field Power
Wire Size
6
10
10
6
6
10
6
10
10
6
6
10
8
6
10
6
6
10
8
10
10
Manual 2100-720C
Page
Ground
Wire Size
10
10
10
10
10
10
10
33 of 42