Bard WA7013 Installation Instructions Manual

Wall mounted package air conditioners

Advertisement

Quick Links

INSTALLATION INSTRUCTIONS
WALL MOUNTED
PACKAGE AIR CONDITIONERS
Bard Manufacturing Company
Bryan, Ohio 43506
Since 1914...Moving ahead just as
planned.
Model
WA7013
Manual :
2100-359B
Supersedes:
2100-359A
File:
Volume III Tab 16
Date:
05-13-02
© Copyright 2002

Advertisement

Table of Contents
loading

Summary of Contents for Bard WA7013

  • Page 1 INSTALLATION INSTRUCTIONS WALL MOUNTED PACKAGE AIR CONDITIONERS Model WA7013 Manual : 2100-359B Bard Manufacturing Company Supersedes: 2100-359A Bryan, Ohio 43506 File: Volume III Tab 16 Since 1914...Moving ahead just as Date: 05-13-02 planned. © Copyright 2002...
  • Page 2: Table Of Contents

    Contents Start Up ..............15 Getting Other Information and Publications ..1 Important Installer Note ......... 13 Crankcase Heaters ..........13 Wall Mount General Information ......2 High Pressure Switch ..........13 Air Conditioning Wall Mount Model Nomenclature .. 2 Three Phase Scroll Compressor Start Up .....
  • Page 3: Getting Other Information And Publications

    Getting Other Information and Publications For more information, contact these These publications can help you install the air conditioner publishers: or heat pump. You can usually find these at your local library or purchase them directly from the publisher. Be sure to consult current edition of each standard.
  • Page 4: Wall Mount General Information

    WALL MOUNT GENERAL INFORMATION AIR CONDITIONING WALL MOUNT MODEL NOMENCLATURE CONTROL MODULES MODEL NUMBER CAPACITY COIL OPTIONS 60 - 5 Ton X - Standard REVISIONS 1 - Phenolic Coated Evaporator COLOR OPTIONS 2 - Phenolic Coated Condenser X - Beige (Standard) 3 - Phenolic Coated Evaporator FEATURE CODE 1 - White...
  • Page 5: Figure 1 Unit Dimensions

    FIGURE 1 UNIT DIMENSIONS MIS-1456...
  • Page 6: Table 2 Electrical Specifications

    TABLE 2 ELECTRICAL SPECIFICATIONS & Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors. Based on 75° C copper wire. All Wiring must conform to NEC and all local codes. These “minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to the National Electric Code (latest revision), article 310 for power conductor sizing.
  • Page 7: Shipping Damage

    Any grille that meets with 5/8 inch louver criteria may be on heat loss calculation made according to methods of used. It is recommended that Bard Return Air Grille Kit Air Conditioning Contractors of America (ACCA). The RG2 through RG5 or RFG2 through RFG5 be installed air duct should be installed in accordance with the when no return duct is used.
  • Page 8: Installation Instructions

    INSTALLATION INSTRUCTIONS WALL MOUNTING INFORMATION WARNING 1. Two holes for the supply and return air openings must be cut through the wall as shown in Figure 1. 2. On wood frame walls, the wall construction must be Failure to provide the 1/4 inch clearance strong and rigid enough to carry the weight of the unit between the supply duct and a combustible without transmitting any unit vibration.
  • Page 9: Figure 2 Mounting Instructions

    FIGURE 2 MOUNTING INSTRUCTIONS MIS-1445...
  • Page 10: Figure 3 Electric Heat Clearance

    FIGURE 3 ELECTRIC HEAT CLEARANCE SIDE SECTION VIEW OF SUPPLY AIR DUCT FOR WALL MOUNTED UNIT SHOWING 1/4 INCH CLEARANCE TO COMBUSTIBLE SURFACES. MIS-277 WARNING minimum of 1/4 inch clearance must be maintained between the supply air duct and combustible materials. This is required for the first 3 feet of ducting.
  • Page 11: Figure 4 Wall Mounting Instructions

    FIGURE 4 WALL MOUNTING INSTRUCTIONS WALL STRUCTURE SEE FIGURE 3 – MOUNTING INSTRUCTIONS FACTORY SUPPLIED RAIN FLASHING. MOUNT ON UNIT BEFORE INSTALLATION. SUPPLY AIR SUPPLY AIR SUPPLY AIR OPENING OPENING OPENING RETURN AIR RETURN AIR RETURN AIR OPENING OPENING OPENING BOTTOM MOUTING BRACKET.
  • Page 12: Figure 6 Common Wall Mounting Installations

    FIGURE 6 COMMON WALL MOUNTING INSTALLATIONS FREE AIR FLOW NO DUCT DUCTED SUPPLY RETURN AT UNIT CLOSET INSTALLATION FALSE WALL INSTALLATION MIS-550 Manual 2100-359 Page 10...
  • Page 13: Wiring - Main Power

    WIRING – MAIN POWER See “Start Up” section for important information on three phase scroll compressor start ups. Refer to the unit rating plate for wire sizing information and maximum fuse or “HACR” type circuit breaker size. Each outdoor unit is marked with a “Minimum Circuit WIRING –...
  • Page 14: Figure 7 Unit 24V Terminal Board

    FIGURE 7 UNIT 24V TERMINAL BOARD MIS-1373B Manual 2100-359 Page 12...
  • Page 15: Start Up

    START UP SERVICE HINTS IMPORTANT INSTALLER NOTE 1. Caution homeowner to maintain clean air filters at all For improved start up performance wash the indoor coil times. Also, not to needlessly close off supply and with a dish washing detergent. return air registers.
  • Page 16: Adjustments

    High Pressure Switch and Lockout Sequence ADJUSTMENTS Adjustable Delay on Make and Delay on Break If the high pressure switch opens, the compressor Timer contactor will de-energize immediately. The lockout timer will go into a soft lockout and stay in soft lockout The potentiometer is used to select Delay on Break time until the high pressure switch closes and the delay on from 30 seconds to 5 minutes.
  • Page 17: Figure 8 Fan Blade Setting

    TROUBLESHOOTING FAN BLADE SETTING DIMENSIONS 5. Slide complete motor, fan blade, and shroud assembly out the left side of the unit. Shown in Figure 10 is the correct fan blade setting dimension for proper air delivery across the outdoor coil. 6.
  • Page 18: Pressure Table

    TABLE 10 PRESSURE TABLE COOLING Air Temperature Entering Outdoor Coil °F Low side pressure ± 2 PSIG High side pressure ± 5 PSIG Tables are based upon rated CFM (airflow) across the evaporator coil. If there is any doubt as to correct operating charge being in the system, the charge should be removed, system evacuated and recharged to serial plate instructions.

Table of Contents