CONTENTS Getting Other Information and Publications Start Up For more information, contact these publishers: ..3 Important Installer Note ......... 16 Crankcase Heaters ..........16 Wall Mount General Information High Pressure Switch ..........16 Air Conditioner Wall Mount Model Nomenclature ..4 Three Phase Scroll Compressor Start Up Shipping Damage ............
Getting Other Information and Publications These publications can help you install the air FOR MORE INFORMATION, CONTACT conditioner or heat pump. You can usually find these at THESE PUBLISHERS: your local library or purchase them directly from the publisher. Be sure to consult current edition of each standard.
WALL MOUNT GENERAL INFORMATION AIR CONDITIONER WALL MOUNT MODEL NOMENCLATURE – REVISION CONTROL MODULES MODEL NUMBER J – Standard on all CAPACITY Models VOLTS & PHASE COLOR OPTIONS 61 – 5 Ton A – 230/208-1 X – Beige (Standard) 70 – 6 Ton B –...
Any grille that meets the 5/8 inch louver criteria, may be air duct should be installed in accordance with the used. It is recommended that Bard Return Air Grille Kit Standards of the National Fire Protection Association for RG-2 through RG-5 or RFG-2 through RFG-5 be the Installation of Air Conditioning and Ventilating installed when no return duct is used.
FILTERS All capacity, efficiency and cost of operation information as required for Department of Energy A 1-inch throwaway filter is supplied with each unit. “Energyguide” Fact Sheets is based upon the fresh air The filter slides into position making it easy to service. blank-off plate in place and is recommended for This filter can be serviced from the outside by removing maximum energy efficiency.
INSTALLATION INSTRUCTIONS WALL MOUNTING INFORMATION 3. Locate and mark lag bolt locations and bottom mounting bracket location. See Figure 4. 1. Two holes, for the supply and return air openings, 4. Mount bottom mounting bracket. must be cut through the wall as shown in Figure 3. 5.
The unit rating plate lists a “Maximum Time Delay in the bottom left hand corner of the disconnect opening Relay Fuse” or “HACR" type circuit breaker that is to be under the disconnect access panel straight out. This tab used with the equipment. The correct size must be used will now line up with the slot in the door.
NOTE: The voltage should be measured at the field WIRING — LOW VOLTAGE WIRING power connection point in the unit and while 230/208V, 1 phase and 3 phase equipment dual primary the unit is operating at full load (maximum voltage transformers. All equipment leaves the factory amperage operating condition).
FIGURE 4 WALL-MOUNTING INSTRUCTIONS SEE FIGURE 3 — MOUNTING INSTRUCTIONS FIGURE 5 WALL-MOUNTING INSTRUCTIONS SEE UNIT DIMENSIONS, FIGURE 1, FOR ACTUAL DIMENSIONS SEE FIGURE 1 FOR DUCT DIMENSIONS Manual 2100-425B Page 12 of 21...
FIGURE 7 ELECTRIC HEAT CLEARANCE Side section view of supply air duct for wall mounted unit showing 1/4 inch clearance to combustible surfaces. WARNING • A minimum of 1/4 inch clearance must be maintained between the supply air duct and combustible materials. This is required for the first 3 feet of ducting.
All three The decal in Figure 9 is affixed to all WA611, WA70 phase units incorporate a phase monitor to ensure proper and WA721 units detailing start-up procedure. This is field wiring.
High Pressure Switch and Lockout Sequence SERVICE HINTS If the high pressure switch opens, the compressor 1. Caution homeowner to maintain clean air filters at contactor will de-energize immediately. The lockout all times. Also, not to needlessly close off supply timer will go into a soft lockout and stay in soft lockout and return air registers.
ADJUSTMENTS PHASE MONITOR All units with three phase scroll compressors are Adjustable Delay on Make and Delay on Break equipped with a 3 phase line monitor to prevent Timer compressor damage due to phase reversal. The potentiometer is used to select Delay on Break time The phase monitor in this unit is equipped with two from 30 seconds to 5 minutes.
TROUBLESHOOTING FAN BLADE SETTING DIMENSIONS REFRIGERANT CHARGE The correct system R-22 charge is shown on the unit Shown in the drawing below are the correct fan blade rating plate. Optimum unit performance will occur with setting dimensions for proper air delivery across the a refrigerant charge resulting in a suction line outdoor coil.