To reduce false alarms caused by system power up (or by power supply restoration after both
mains supply and AUX power supply fail), the AMAX panel is does not perform zone tests
within one minute after the system power up.
5.4

System Status Indicator

The AMAX panel indicates the system status by using the LED status indicator on the system
main board.
Slow flash of red on status indicator (repeating on and off with an interval of one second)
indicates a normal system operation.
5.5

Certification

Prerequisites for Certification Conform Installation
The AMAX panel is certified. To realize a usage of the system conformable to the certification
described in this chapter, the following prerequisites have to be fulfilled:
Bosch Sicherheitssysteme GmbH
Use one of the following possibilities for devices:
Two supervised warning devices (PO-1 PO-2 & PO+) and one ATS 2 communicator
(onboard dialer, B426, D4020 or DX4020G)
One self powered warning device and one ATS 2 communicator (onboard dialer,
B426, D4020 or DX4020G)
Two communicators, one ATS 2 (onboard dialer, B426, D4020 or DX4020G) and one
ATS 1 (onboard dialer, B426, D4020 or DX4020G)
One ATS 3 communicator (DX4020 or B426)
Connect all communicators to a central monitoring station.
Only use the onboard dialer and the option bus communicator for alarm transmission.
Connect one 12V / 7AH or one 12V / 18Ah battery to the system.
Ensure the maximum current for all components with a 7Ah Battery to be 550mA.
Ensure the maximum current for all components with a 18Ah Battery to be 1500mA
(standby 12h, recharge battery 80% in 72h) (PCB =l 00mA, IUI-AMAX Keypads = 31mA,
DX2010 = 35mA, DX3010 = 10mA, B426 = 100mA, B450 = 180mA, DX4020G = 65mA,
RF3227E = 30mA, RFRC-OPT = 30mA).
Make sure to have an indication of the arm / disarm status accessible from outside the
monitored area (this indication can be time limited).
Use one of the following methods for the access to the monitored area:
Starting the entry procedure by opening a door
Indicating the arm / disarm status
Preventing the access to the monitored area (e.g. mechanical door strike)
Only use the enclosure lock only in non EN setup.
Only use the telephone arming in non EN setup.
Only mount additional modules (except input module DX2010) inside the enclosure.
Install the tamper skirt on the PCB of the input module DX2010, if the input module
DX2010 is mounted on the external enclosure (AE20).
Program the system with the EN settings indicated on the programming sheet.
Remove the EN indication (on label) if the system is set without EN parameters.
Connect no more than 10 devices to one zone input (Panel, Keypad, Input Module, RFUN,
...)
Installation Manual
Installation | en
29
2015.05 | 06 | F.01U.309.277