Table 6.1: The value ranges of output event options
* AMAX 2100 areas 1 - 2 zones 1 - 8
AMAX 3000 / 3000 BE areas 1 - 8 zones 1 - 32
AMAX 4000 areas 1 - 16 zones 1 - 64
Output Events – Detailed description
00 - Not Used
01 – System Disarmed
The output is operated in the following cases:
The output is reset in the following cases:
02 - System Armed
The output is operated in the following cases:
The output is reset in the following cases:
If the output time is set to 000, the output will continue until the system is disarmed.
03 - System Alarm
This output is operated when an alarm occurs.
The output is reset in the following cases:
Bosch Sicherheitssysteme GmbH
Verified Alarm
Unverified Alarm
Technical Alarm
Bypassed Zone
Ready to Arm
Walk Test Output Mode
24h Alarm
24h Panic Alarm
Medical Alarm
RF Power Fault
Follow Zone
Schedule
The system is disarmed after a system reset.
The system operated the disarm command.
The system is armed.
The programmed output time ends.
The system is armed after a system reset.
The system operated the arm command. (After the exit time ends.)
The system is disarmed.
The programmed output time ends.
The system is disarmed and alarm is reset.
Installation Manual
Settings | en
0 = All areas 1 – 16 = Areas 1 – 16*
0 = Any area
1 – 16 = areas 1 – 16
0 = Any repeater
0 = Any area
1 – 16 = areas 1 – 16
2015.05 | 06 | F.01U.309.277
77