Ventilation Settings
The Ventilation Settings screens are used to view/edit settings associated with a whole home venti-
lator (ERV/HRV) devices. These screens are only accessible in system which have an ERV/HRV
Accessory control installed. The settings available are explained in the table below.
The installer must also add the ventilation device through the Edit/Add device screen (as
described previously).
Variable
Ventilation Mode
Ventilation
Runtime
per Cycle
Ventilation Cycle
Time
Ventilation
Limits
No Ventilation
Above
No Ventilation
Below
11:07AM Thu 21 Jul
Ventilation Settings
Ventilation with a
Ventilation per
heating call
Installer settings
10
0
5 10
15
20 2530
35
11:07AM Thu 21 Jul
Ventilation Settings
No ventilation is the outdoor
temperature is above 50F and
above the selected indoor humidity
50%
40
45 50 55 60
Johnson Controls Unitary Products
Default
Settings
Continuous,
Timed
Timed or Off
5-55 min in
20 min.
5 min intervals
1 hour
1 -4 hours
Disabled,
Disabled
Default,
and Manual
100 F
0 F
Ventilation with a
cooling call
85
40
8590
95
100
Back
65
Back
NOTICE
Explanation
This will determine how often the ventilation
device will be opened
If ventilation mode is set to "Timed", the control
will allow ventilation per this setting per Ventila-
tion Cycle Time
If ventilation mode is set to "Timed", the control
will allow Ventilation Runtime per this setting
If there is a damper installed for ventilation pur-
poses
The touch screen will not allow ventilation if the
outdoor temperature exceeds this setting
The touch screen will not allow ventilation if the
outdoor temperatures is below this setting
There are additional settings for ventilation that
are covered with a temperature slider. These set-
tings will determine if the ventilator is opened
during a call for conditioning. The Touch Screen
Communicating Control will open ventilation any
time there is a call for conditioning if the outdoor
temperature falls in the "Ventilation with a heat-
ing/cooling call". Otherwise ventilation will run
with the indoor blower per the previously
described settings.
Finally the ventilation can be controlled per
indoor humidity. If the outdoor temperature is
above 50 degrees the touch screen can be set
so that it will disable ventilation if the indoor
humidity rises above the desired setting.