Unit Model Number Description

Digit 1, 2, 3, 4 – Unit Model
CGAF = Air-Cooled Scroll – Chiller
CXAF = Air-Cooled Scroll – Heat Pump
Digit 5-7 – Unit Nominal Tonnage
080 = 80 Tons
090 = 90 Tons
100 = 100 Tons
110 = 110 Tons
130 = 130 Tons
140 = 140 Tons
150 = 150 Tons
165 = 165 Tons
180 = 180 Tons
190 = 190 Tons
Digit 8 – Unit Voltage
D = 400V/50Hz/3ph
G = 400V/50Hz/3ph Compatible with IT Neutral
Digit 9 – Manufacturing Location
E = Epinal
F = Epinal (ICS)
Digit 10, 11 – Design Sequence
** = Factory assigned
Digit 12 – Efficiency
A = Extra Efficiency
H = High Efficiency (With SLHX), 4V/5V/6V
N = Standard Efficiency, 4V/5V/6V
R = High Heat Efficiency, 4V/5V/6V
U = Standard Efficiency (Compact), 3V
V = High Efficiency (Compact, with SLHX), 3V
W = High Heat Efficiency (Compact), 3V
Digit 13 – Agency Listing
C = CE Marking
Digit 14 – Pressure Vessel Code
2 = PED (Pressure equipment directive)
Digit 15 – Acoustic Level
X = Standard Noise (SN)
L = Low Noise (LN)
E = Extra Low Noise (XLN)
Digit 16 – Unit Application
X = Standard Ambient [-10°C; 46°C]
L = Low Ambient [-20°C; 46°C]
H = High Ambient [-10°C; 52°C]
D = Wide Ambient [-20°C; 52°C]
1 = Comfort application, cooling mode [10°C; 46°C] and
heating mode [-15°C; 20°C]
3 = Process application, cooling mode [-20°C; 46°C]
Heating mode [-15°C; 35°C]
Digit 17 – Relief Valve Option
W = Without
Digit 18 – Water Connection
X = Grooved pipe connection
W = Grooved pipe + welded coupling
2 = Grooved pipe with coupling and flange adapter
Digit 19 – Evaporator Application
N = Standard cooling [4°C; 20°C]
P = Low temperature process [-12°C; 4°C]
C = Ice making [-7°C; 20°C] with hardwired interface
6
Digit 20 – Evaporator Configurations
B = Brazed plate heat exchanger
T = Shell & Tube heat exchanger
Digit 21 – Thermal Insulation
N = Standard
Digit 22 – Condenser Coating
N = Aluminium Micro Channel
C = E-Coated Micro Channel
B = Aluminium Hydrophilic (blue) coating
E = Epoxy Coated Aluminium Fins (gold)
Digit 23 – Heat Recovery
X = No Heat Recovery
P = Partial Heat Recovery
T = Total Heat Recovery (full equipment)
Digit 24 – Hydraulic Module
X = Pump signal On/Off
1 = Dual pump standard pressure
2 = Single pump standard pressure
3 = Dual pump high pressure
4 = Single pump high pressure
Digit 25 – Free-Cooling
X = No Free-Cooling
F = Total Free-Cooling Direct
H = Total Free-Cooling Glycol free
Digit 26 – Disconnect Switch
B = With circuit breaker
Digit 27 – Under/Over Voltage
X = None
1 = Included
2 = Included with ground fault protection
Digit 28 – Human Interface language
C = Spanish
D = German
E = English
F = French
H = Dutch
I = Italian
M = Swedish
P = Polish
R = Russian
T = Czech
U = Greek
V = Portuguese
2 = Romanian
6 = Hungarian
8 = Turkish
Digit 29 – Smart Com Protocol
X = None
B = BACnet interface
M = Modbus interface
L = LonTalk interface
Digit 30 – Communication Customer
X = None
A = External set point & capacity outputs
Digit 31 – Flow Switch
X = None
F = Field installed flow switch
CG-SVX039C-GB