Trane SINTESIS ADVANTAGE CGAF Series Installation Operation & Maintenance page 66

Air-cooled scroll chillers, air to water scroll heat pumps
Hide thumbs Also See for SINTESIS ADVANTAGE CGAF Series:
Table of Contents

Advertisement

Optional Free-Cooling
Glycol Free-cooling
Free-Cooling Bypass Valve Settings
Position 1:
0% - Closed – Free-cooling
Position 2:
10%
Position 3:
20%
.....
Position 10: 100% - Fully Open – No Free-cooling
Open position: Water flow is directed to evaporator and
there will not be any free-cooling.
Closed position: All the water flow is directed to free-
cooling exchanger or de coupling bottle. In Free-cooling
mode water flow will see highest pressure drop.
Slightly open: 0% to 30% will direct the some portion of
water through free-cooling exchanger and the remaining
to evaporator.
Refer the settings table for more details.
Table 18 – Direct Free-Cooling Setting
DIRECT FC
80
% Open
0%
Position
1/2*
Table 19 – Glycol Free Free-Cooling Setting
DIRECT FC
80
% Open
0%
Position
1/2
Note for maintenance: Check glycol circuit pressure before free-cooling operation season starts. Run glycol pump
few minutes in manual override during monthly maintenance operation when free-cooling is continuously OFF to
avoid possible glycol crystallization. Pump Override function is located in TD7 via Button Settings -> Manual Control
Settings -> Free-cooling Pump Override.
66
90
100
110
0%
0%
0%
1/2
1/2
1/2
90
100
110
0%
0%
0%
1/2
1/2
1/2
130
140
150
20%
30%
30%
3
4
4
130
140
150
20%
20%
20%
3
3
4
165
180
190
30%
40%
40%
4
5
5
165
180
190
30%
30%
30%
4
4
4
CG-SVX039C-GB