Preparing for installation
Delivery and siting
The Vitocal 300-G/W Pro SPS is delivered as a
■
standard unit only. The side panels are supplied on a
separate pallet.
■
The programming unit of the Vitotronic SPS is deliv-
ered inside the wiring chamber and must be fitted
and connected on site (page 43).
Unloading and handling
Note
Before unloading, have the recipient check the con-
signment for possible damage. Note down any dam-
age on the delivery note and notify the haulage con-
tractor.
Lifting gear, such as slings and cross beams, must
■
be provided on site.
■
The lifting capacity of each sling and that of the cross
beam must be at least equal to the shipping weight;
see chapter "Specification".
■
Only use suitable equipment for unloading the lorry;
see the following chapter.
!
Please note
Prevent appliance damage when unloading and
handling the heat pump:
■
Never put weight on top of the appliance.
In order to protect the paintwork, cover lifting
■
tackle (e.g. ropes, cross beam) and insert pad-
ding between the Vitocal 300-G Pro SPS/
Vitocal 300-W Pro SPS and the lifting tackle.
■
Observe correct weight distribution when lift-
ing. The centre of gravity of the
Vitocal 300-G Pro SPS/
Vitocal 300-W Pro SPS lies through the heat
exchanger on the l.h. side.
Avoid impact and shocks to prevent damage
■
to the internal pipework of the heat pump.
■
Avoid tilting the compressor at a sharp angle,
to protect the refrigerant circuit: Max. heat
pump tilting angle 30°. After the heat pump
has been tilted, wait for at least 4 hours before
switching it on.
Handling by crane
Note
The unit must always be transported without the side
and front panels fitted, to avoid damaging them.
8
Accessories are delivered separately.
■
■
The Vitocal 300-G Pro SPS/Vitocal 300-W Pro SPS
are filled with oil and charged with refrigerant at the
factory.
KWT Kälte-Wärmetechnik AG, a member of the
Viessmann Group, will not accept any liability for
damage resulting from inappropriate handling.