Commissioning, inspection, maintenance
Commissioning the system
Correct setting of parameter "Factor set room
curve/heating curve change"
This factor determines the relationship between the
room temperature adjustment and the necessary modi-
fication of the flow temperature.
Theory: This factor is required as the room tempera-
ture is always below the flow temperature.
Optimal factor adjustment: Determine the value by
which the flow temperature needs to be increased in
order to achieve a 1 °C rise in room temperature. For a
description of capturing the outside temperature, see
page 71.
Select menu
å
Select "System"
Select "Heating circuits"
Select "Room 1"
Heating circuit adjustments for the user
Plant
Room temperature
Day:
20.0 °C
Night:
16.0 °C
Clock: Day - operation
Monday
05:00
Tuesday
05:00
Wednesday
05:00
Thursday
05:00
Friday
05:00
Saturday
05:00
Sunday
05:00
Fig.59

Instructing the system user

The system installer should hand the operating instruc-
tions to the system user and instruct the user in oper-
ating the system.
This includes all components installed as accessories,
e.g. remote control units. In addition, the system instal-
ler must make the user aware of the required mainte-
nance work.
Please refer to the "Vitotronic SPS operating
instructions" for further details of the operation.
72
Room 1
13:18:56
17/04/2013
Holiday program
-
22:00
h
-
22:00
h
-
22:00
h
-
h
22:00
-
h
22:00
-
h
22:00
-
h
22:00
(cont.)

Cooling circuits

The cooling curve results from: outside temperature
and set cooling temperature. This means only one off-
set and one slope can be adjusted.
Cooling circuits are regulated and adjusted in the
same way as heating circuits (Please note: observe
the difference described above).