Viessmann Vitocrossal 200 Service Instructions For Contractors page 75

Gas condensing boiler with matrix radiant burner permissible operating pressure 6 bar (0.6 mpa)
Hide thumbs Also See for Vitocrossal 200:
Table of Contents

Advertisement

Specification
(cont.)
Rated heating output
T
/T
= 50/30
F
R
T
/T
= 80/60
F
R
Flue gas parameters
*2
Temperature (at a return temper-
ature of 30 °C)
At rated heating output
At partial load
Temperature (at a return temper-
ature of 60 °C)
Mass flow rate (for natural gas)
At rated heating output
At partial load
Available draught
At the flue outlet
*3
Flue gas connection
Draught at the flue outlet
Product parameters according
to EnEV
Standard seasonal efficiency
[to DIN]
At heating system temperature
40/30 °C
At heating system temperature
75/60 °C
Standby loss qB,70
Sound pressure level
*4
1 m in front of the boiler (full
load)
MatriX radiant burner
Rated heat input
Upper
Lower
Burner type
Voltage
Frequency
Power consumption
Upper rated heating output
Lower rated heating output
Modulation range
*2
Calculation values for sizing the flue system to EN 13384, based on 10 % CO
Flue gas temperatures as actual gross values at 20 °C combustion air temperature.
The details for partial load refer to an output of 33 % of the rated heating output. If the partial load differs (subject to burner
operating mode), calculate the flue gas mass flow rate accordingly.
*3
If using the Vitocrossal 200 with moisture-resistant chimneys, the draught must be no more than 0 Pa.
Standard values resulting from sound pressure level testing cannot be guaranteed, as sound pressure level tests are al-
*4
ways dependent on the specific system.
kW
29 - 87
38 - 115
kW
27 - 80
35 - 105
°C
45
°C
35
°C
75
kg/h
126
kg/h
42
Pa
70
mbar
0.7
mm
160
7
Pa
70
mbar
0.7
%
%
%
0.6
dB(A)
44
kW
82
kW
27
V
230
Hz
50
W
75
W
25
%
33-100
47 - 142
47 - 186
43 - 130
43 - 170
45
45
35
35
75
75
166
207
56
69
70
70
0.7
0.7
160
160
70
70
0.7
0.7
Up to 98 (Hs) [gross cv]
Up to 96 (Hs) [gross cv]
0.5
0.4
48
51
109
134
36
45
CM2B
230
230
50
50
140
185
40
45
33-100
33-100
25-100
for natural gas.
2
Specification
82 - 246
104 - 311
75 - 225
95 - 285
45
45
45
35
35
35
75
75
75
269
358
452
69
119
150
70
70
70
0.7
0.7
0.7
200
200
200
70
70
70
0.7
0.7
0.7
0.4
0.3
0.3
58
60
61
176
232
293
44
77
98
230
230
230
50
50
50
270
330
385
45
50
55
33-100
33-100
75