Commissioning, inspection, maintenance
5. Reinstall control cables using clamps. For connec-
tion diagrams, see following pages.
!
Please note
Incorrectly connected control cables can
cause malfunctions.
Ensure that control cables are connected
correctly.
6. Check control cables:
Correct connection and kink-free routing
Application and seating of retaining clips
7. Tighten fitting
C
Danger
Escaping gas leads to a risk of explosion.
Check the fitting and gasket between the fan
housing and the boiler door for gas tight-
ness.
d
Boiler door
D
Fan
E
on gas supply pipe
D
.
D
E
F
e