Checking the CO
Permissible CO
content
2
Gas type
CO
con-
2
tent
at
Natural gas
Upper heat-
E
ing output
(100 %)
Lower heat-
ing output
(0 %)
Natural gas
Upper heat-
H
ing output
(100 %)
Lower heat-
ing output
(0 %)
Natural gas
Upper heat-
LL
ing output
(100 %)
Lower heat-
ing output
(0 %)
Natural gas
Upper heat-
L
ing output
(100 %)
Lower heat-
ing output
(0 %)
CO
test at the upper heating output (87 kW)
2
Fig. 10
content
(cont.)
2
87
115
7.1 - 10.2 % 7.0 - 10.1 % 7.0 - 10.1 % 7.1 - 10.2 % 7.1 - 10.2 %
Actual value at upper heating output minus
0.3 - 0.7 %
0.3 - 0.7 %
8.0 - 10.2 % 7.9 - 10.1 % 7.9 - 10.1 % 8.0 - 10.2 % 8.0 - 10.2 %
Actual value at upper heating output minus
0.3 - 0.7 %
0.3 - 0.7 %
7.2 - 10.0 %
7.1 - 9.9 %
Actual value at upper heating output minus
0.3 - 0.7 %
0.3 - 0.7 %
8.3 - 10.0 %
8.2 - 9.9 %
Actual value at upper heating output minus
0.3 - 0.7 %
0.3 - 0.7 %
Commissioning, inspection, maintenance
Rated heating output in kW
142
186
0.3 - 0.7 %
0.4 - 0.8 %
0.3 - 0.7 %
0.4 - 0.8 %
7.1 - 9.9 % 7.2 - 10.0 % 7.2 - 10.0 %
0.3 - 0.7 %
0.4 - 0.8 %
8.2 - 9.9 % 8.3 - 10.0 % 8.3 - 10.0 %
0.3 - 0.7 %
0.4 - 0.8 %
1. Press
until the service display has counted up to
"100" (= 100 %).
2. Check the CO
content at the flue pipe.
2
For permissible CO
2
3. Check control cables:
■
Connection and kink-free routing
■
Application and seating of retaining clips
Note
The unconnected end of the hose is open in open
flue operation. For room sealed operation, the end
of the hose is pushed onto the intake adaptor.
246
7.1 - 10.2 %
0.4 - 0.8 %
0.4 - 0.8 %
8.0 - 10.2 %
0.4 - 0.8 %
0.4 - 0.8 %
7.2 - 10.0 %
0.4 - 0.8 %
0.4 - 0.8 %
8.3 - 10.0 %
0.4 - 0.8 %
0.4 - 0.8 %
content, see above table.