Checking the high limit safety cut-out setting

The high limit safety cut-out must not be set higher
than 110 °C; if required, set it to a maximum of 110 °C.

Filling the heating system with water and venting

Record the volume filled, water hardness and pH value
on page 72.

Filling the trap with water

Fig. 1

Commissioning the system

Danger
CO build-up as a result of incorrect burner
adjustment can have serious health implications.
Always carry out a CO test before and after
work on gas appliances.
Commissioning, inspection, maintenance
Control unit installation and service instructions
Note
Observe the "Water quality requirements" on
page 70.
1. Undo the trap and fill it with water. There is a risk of
flue gas escaping if it is not filled with water prior to
commissioning.
2. Check that the condensate can drain freely.
3. Refit the trap.
Vitotronic operating instructions and service
instructions
Neutralising system operating instructions
Flue system installation instructions