Connecting Method - Vivax HPS-42HM84AERI/I1s User Manual

Table of Contents

Advertisement

VIVAX
Connecting method 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Max. Difference in height
 
 
 
 
 
 
 
 
The largest level difference between indoor unit and outdoor unit should not exceed 
 
20m (if the outdoor unit is above) or 15m (if the outdoor unit is below). Additionally:
 
(i)  If  the  outdoor  unit  is  above  and  the  level  difference  is  greater  than  20m,  it  is
 
recommended that an oil return bend with dimensions as specified in Figure 7‐4 is set 
 
every 5m in the gas pipe of the main pipe; and (ii) if the outdoor unit is below and the
 
level difference is more than 15m, the liquid pipe of the main pipe  should be increased
 
one size. 
 
 
 
 
Size of pipes of Gas side and Liquid  s ide
1)
 
MODEL 
4/6kW 
8/10kW 
1‐phase 12/14/16kW 
3‐phase 12/14/16kW 
 
 
Outdoor unit
 
 
Fig. 7‐5
Refrigerant 
R32 
R32 
R32 
R32 
 CAUTION 
 
Gas side/Liquid side 
Φ15.9 / Φ6.35 
Φ15.9 / Φ9.52 
Φ15.9 / Φ9.52 
Φ15.9 / Φ9.52 
20 