TABLE 2 – COMPRESSOR DATA
DXS45LA – MOTOR CODE A
VOLTAGE CODE
-17
MAX kW
150 150 150 150 113 150 150 150 150 150 113 150 105 105 105 105
MAX AMPS
492 428 259 214 193 171 492 428 259 214 193 171 338 294 178 147 135 118
TABLE 3 – FAN DATA (-46)
FAN TYPE
STANDARD
HIGH PRESSURE
JOHNSON CONTROLS
ELECTRICAL DATA
MAXIMUM kW AND AMPERAGE VALUES FOR DXST COMPRESSORS
COMPRESSOR MODEL AND VOLTAGE CODE
(B5N, B5E, B6N, B6E)
-28
-40
-46
-50
-58
NOMINAL POWER
(kW)
1.57
3.7
DXS36LA – MOTOR CODE A
(A5N, A5E, A6N, A6E)
-17
-28
-40
-46
-50
-58
FULL LOAD AMPS
(FLA)
4.4
6.8
FORM 201.18-NM7
DXS24LA – MOTOR CODE (TBD)
(C5N, C5E, C6N, C6E)
-17
-28
-40
-46
-50
80
LOCKED ROTOR AMPS
(LRA)
18.0
46.3
-58
105
7