Deep Bottom Pans (Optional) - Siemens 8BT2 Installation And Operating Instructions Manual

Extendable truck- type circuit-breaker switchgear
Table of Contents

Advertisement

4.3.9.1.3.
64
Fasten cable lugs at cable bracket (use antimagnetic clamps for single-core cables)
with M12 bolts.
Lead earthing of cable termination to earthing busbar and bolt tight.

Deep bottom pans (optional)

NOTE!
Deep bottom pans are used in conditions below:
1. Three core power cable is entered to the panel and phases are separated inside
the panel.
2. The cable termination length is longer than the limited value in the application
(please see fig54 & 55 on page55 & 56).
nd
Note: If the 2
condition is valid, please consult SIEMENS to arrange the exact
dimensions of deep bottom pan according to the cable termination. This is not a
standard application.
Deep bottom pan is available as supplementary equipment for the switchgear.
Fig76. Side view of deep bottom pan with standard dimensions
Revision 04 * INSTALLATION AND OPERATING INSTRUCTIONS 8BT2 * 881-4027.9