Trouble Shooting - Siemens 8BT2 Installation And Operating Instructions Manual

Extendable truck- type circuit-breaker switchgear
Table of Contents

Advertisement

8.

TROUBLE SHOOTING

Fault
1) Truck can not be moved out of
panel.
2) Door to switching device
compartment.
Fault
Double bit key can not be turned
with open door locking handle.
Truck ca not be racked to
SERVICE position (mechanically).
Truck can not be racked to TEST
position.
Double bit key can not be turned.
Fault
Operating lever for earthing switch
can not be pushed in.
Fault
Circuit breaker can not be closed
Spring energy store is not
charged automatically
92
• Fiber-reinforced plastics
• Rubber materials
• Ceramic materials
• Lubricants
• Bolts, washers, nuts, rivets
As delivered by Siemens, the switchgear does not contain hazardous materials as per the
Hazardous Material Regulations applicable in the Federal Republic of Germany. In other
countries, the locally applicable laws and regulations must be followed.
Should you require further information, please contact your regional SIEMENS representative.
Truck interlocking
Cause
Truck interlock closed
Interlocking lever of LV connector not
folded inwards
Locking gates of guide rails not closed
Truck
Cause
Circuit breaker in CLOSED position
Operating lever inserted in manual
CLOSE/OPEN operating mechanism of
feeder earthing switch
Feeder earthing switch not in OPEN
position
General switchgear interlock active
Circuit breaker in CLOSED position
Feeder earthing switch
Cause
Switching device truck in SERVICE
position
Hand crank for switching device truck
inserted
Electromagnetic interlocking is active
Circuit breaker
Cause
Hand crank for truck inserted
Switching device truck is intermediate
position
Spring not charged
Under voltage release not activated
Low voltage connector not plugged in
No control voltage
Revision 04 * INSTALLATION AND OPERATING INSTRUCTIONS 8BT2 * 881-4027.9
Remedy
Open truck interlock
Fold interlocking lever inwards
Close locking gates of guide rails
Remedy
Switch circuit breaker to OPEN position
Remove operating lever
Switch feeder earthing switch to OPEN
position
Observe general switchgear interlock
Switch circuit breaker to OPEN position
Remedy
Rack switching device truck to TEST
position
Remove hand crank for switching device
truck
Observe the electromagnetic interlocking
Remedy
Remove hand crank for truck
Rack switching device truck to SERVICE
or TEST position
Wait for 15 s (motor) or charge manually
Energize the under voltage release
Plug low voltage connector in
Apply control voltage or charge spring
energy store manually

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents