Viessmann Vitopend 100-W Installation And Service Instructions For Contractors page 44

Gas system and combi boilers for open flue operation natural gas and lpg version
Table of Contents

Advertisement

Troubleshooting
Repairs
(cont.)
20
10
8
6
4
2
1
0,8
0,6
0,4
10
30
50
20
40
Temperature in °C
1. Temperature limiter:
Perform the check if the burner con-
trol unit cannot be reset after a fault
shutdown, although the boiler water
temperature is below approx. 90 °C.
■ Disconnect the leads from the sen-
sor.
■ Check the continuity of the temper-
ature limiter with a multimeter.
■ Remove the faulty temperature lim-
iter.
■ Install a new temperature limiter.
4
3
2
1
To reset, briefly turn rotary selector
"tr" clockwise as far as it will go
and then back again. The ignition
process will then repeat.
44
70
90
110
60
80
100 120
5
6
2. Boiler water temperature sensor:
■ Disconnect the leads from the sen-
sor.
■ Check the sensor resistance and
compare it with the curve.
■ Replace the sensor in the case of
severe deviation.
!
Please note
The boiler water tempera-
ture sensor is immersed in
the heating water (risk of
scalding).
Drain the boiler before
replacing the sensor.
3. Outlet temperature sensor (gas
combi boiler):
■ Disconnect the leads from the sen-
sor.
■ Check the sensor resistance and
compare it with the curve.
■ Replace the sensor in the case of
severe deviation.
Danger
The outlet temperature sen-
sor is immersed in the DHW
(risk of scalding).
Drain the DHW side of the
boiler before replacing the
sensor.