Checking The Static Pressure And Supply Pressure - Viessmann Vitopend 100-W Installation And Service Instructions For Contractors

Gas system and combi boilers for open flue operation natural gas and lpg version
Table of Contents

Advertisement

Commissioning, inspection, maintenance
Further details regarding the individual steps
1. Check the gas type and Wobbe index
(W
) with your gas supply utility or
s
LPG supplier and compare them with
the details above.
2. If the details do not match, convert
the burner to the available gas type,
in accordance with the details provi-
ded by the gas supply utility or your
LPG supplier.
3. Record the gas type in the "Reports"
table.
Wobbe index range W
W
s
Natural gas H
LPG P

Checking the static pressure and supply pressure

Danger
CO formation as a result of incor-
rect burner adjustment can have
serious health implications.
Carry out a CO test before and
after work on gas appliances.
Note
The cover panel must be fitted to prevent
infiltrating air.
Operation with LPG
Purge the LPG tank twice during com-
missioning or replacement. Vent the tank
and gas connection line thoroughly after
purging.
1. Close the gas shut-off valve.
20
s
kWh/m
3
MJ/m
3
12.7 to
45.6 to
15.2
54.8
20.3 to
72.9 to
24.4
87.8
(cont.)
Note
The indicated Wobbe index W
apply to the following ambient condi-
tions:
■ Air pressure: 1013 mbar (101.3 kPa)
■ Temperature: 15 °C
2.
Release the screw inside test con-
nector A on the gas train but do not
remove, then connect the pressure
gauge.
3. Open the gas shut-off valve.
values
s