Viessmann Vitopend 100-W Installation And Service Instructions For Contractors page 37

Gas system and combi boilers for open flue operation natural gas and lpg version
Table of Contents

Advertisement

Function sequence and possible faults
Control unit issues
a heat demand
Yes
Ignition
Yes
Gas train opens
Yes
Ionisation current
builds (higher than
2 µA)
Symbol A
Yes
Burner in opera-
tion
Display
No
No
Fault "F4"
No
Fault "F4"
No
Fault "F4"
No
Shuts down below
the set boiler water
temperature and
restarts immediate-
ly
Troubleshooting
Action
Increase set value
and ensure heat is
drawn off
Check the ignition
module connec-
tion
Check the gas
train (control volt-
age 230 V) and
gas supply pres-
sure
Check the ionisa-
tion current, check
the electrode ad-
justment and the
gas line for air-
locks.
Check the flue sys-
tem for tightness
(flue gas recircula-
tion); check the
gas flow pressure
37