Viessmann Vitoladens 300-C Installation And Service Instructions Manual page 71

Oil condensing boiler with integral boiler control unit
Hide thumbs Also See for Vitoladens 300-C:
Table of Contents

Advertisement

Code 2
(cont.)
Coding in the delivered condition
0F:70
Solar circuit flow rate at max.
pump speed 7 l/min.
10:0
Target temperature control switch-
ed off (see coding address "11").
11:50
Set solar DHW temperature 50 °C.
Target temperature control
switched on (code "10:1"):
Temperature at which the solar
heated water is to be stratified
into the DHW cylinder.
If code "20:9" (heating of 2 DHW
cylinders) is set:
When the set DHW temperature
is achieved in one DHW cylinder,
the second DHW cylinder is
heated.
12:10
Minimum collector temperature
(minimum start temperature for the
solar circuit pump) 10 °C.
20:0
No extended control function ac-
tive.
22:8
Start temperature differential with
central heating backup (code
"20:4" must be set) 8 K.
23:4
Stop temperature differential with
central heating backup (code
"20:4" must be set) 4 K.
24:40
Start temperature for thermostat
function (code "20:5" or "20:6"
must be selected) 40 °C.
25:50
Stop temperature for thermostat
function (code "20:5" or "20:6"
must be selected) 50 °C.
26:1
Priority for DHW cylinder 1 with
cyclical heating.
(Code "20:9" must be set).
Possible change
0F:1
Flow rate adjustable from 0.1 to
to
25.5 l/min.
0F:255
1 step
10:1
Target temperature control switched
on.
11:10
The set solar DHW temperature is
to
adjustable from 10 to 90 °C.
11:90
12:0
No minimum limit active.
12:1
Minimum collector temperature ad-
to
justable from 1 to 90 °C.
12:90
20:1
Additional function for DHW heating.
20:2
Differential temperature control 2.
20:3
Differential temperature control 2
and auxiliary function.
20:4
Differential temperature control 2 for
central heating backup.
20:5
Thermostat function.
20:6
Thermostat function and auxiliary
function.
20:7
Solar heating via external heat ex-
changer without additional tempera-
ture sensor.
20:8
Solar heating via external heat ex-
changer with additional temperature
sensor.
20:9
Solar heating of 2 DHW cylinders.
22:2
Start temperature differential adjust-
to
able from 2 to 30 K.
22:30
23:2
Shutdown temperature differential
to
adjustable from 1 to 29 K.
23:30
24:0
Start temperature for thermostat
to
function adjustable from 0 to 100 K.
24:100
25:0
Stop temperature for thermostat
to
function adjustable from 0 to 100 K.
25:100
26:0
Priority for DHW cylinder 1 without
cyclical heating.
26:2
Priority for DHW cylinder 2 without
cyclical heating.
Codes
0.1 l/min
71