Viessmann Vitoladens 300-C Installation And Service Instructions Manual page 73

Oil condensing boiler with integral boiler control unit
Hide thumbs Also See for Vitoladens 300-C:
Table of Contents

Advertisement

Code 2
(cont.)
Parameter
address A3:...
-7
-6
-5
-4
-3
-2
-1
0
1
2
to
15
Coding in the delivered condition
A4:0
With frost protection
A5:5
With heating circuit pump logic
function (economy mode): Heating
circuit pump is "OFF" when the
outside temperature (OT) is 1 K
higher than the set room tempera-
ture (RT
OT > RT
Parameter address A5:...
1
2
3
4
5
6
7
to
15
Heating circuit pump
"ON"
-8 °C
-7 °C
-6 °C
-5 °C
-4 °C
-3 °C
-2 °C
-1 °C
0 °C
1 °C
to
14 °C
)
set
+ 1 K
set
With heating circuit pump logic function: Heating circuit pump "OFF"
OT > RT
+ 5 K
set
OT > RT
+ 4 K
set
OT > RT
+ 3 K
set
OT > RT
+ 2 K
set
OT > RT
+ 1 K
set
OT > RT
set
OT > RT
1 K
set
OT > RT
9 K
set
"OFF"
-6 °C
-5 °C
-4 °C
-3 °C
-2 °C
-1 °C
0 °C
1 °C
2 °C
3 °C
to
16 °C
Possible change
A4:1
No frost protection; this setting is on-
ly possible if code "A3:-9" has been
set.
Note
Please note for coding address "A3"
A5:0
Without heating circuit pump logic
function
A5:1
With heating circuit pump logic func-
to
tion: Heating circuit pump "OFF"
A5:15
(see the following table)
Codes
73