Electrical Data - Carrier 59MN7B Installation, Start-Up, Operating And Service And Maintenance Instructions

Modulating 4-way multipoise condensing gas furnace
Table of Contents

Advertisement

WARNING
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or death.
Blower door switch opens 115- -v power to control. No
component operation can occur. Do not bypass or close
switch with blower door removed.
VOLTS---
FURNACE SIZE
HERTZ---
PHASE
115--- 60--- 1
060C17--- 14
115--- 60--- 1
060C21--- 20
115--- 60--- 1
080C17--- 14
115--- 60--- 1
080C21--- 20
115--- 60--- 1
100C21--- 22
115--- 60--- 1
120C24--- 22
* Permissible limits of the voltage range at which the unit operates satisfactorily.
# Unit ampacity = 125 percent of largest operating component's full load amps plus 100 percent of all other potential operating components' (EAC, humidifier,
etc.) full load amps.
Time ---delay type is recommended.
{
Length shown is as measured one way along wire path between furnace and service panel for maximum 2 percent voltage drop.
}
W2
COM
W/W1
Y/Y2
R
G
Fig. 33 - - Typical Field Wiring Diagram
Table 9 – Electrical Data
MODULATING
OPERATING VOLTAGE
RANGE*
AMPS
Maximum*
Minimum*
127
104
127
104
127
104
127
104
127
104
127
104
See Fig. 33 for field wiring diagram showing typical field 115- -v
wiring. Check all factory and field electrical connections for
tightness.
Field- -supplied wiring shall conform with the limitations of 63_F
(33_C) rise.
MAX
UNIT
UNIT
AMPACITY#
9.0
12.0
14.1
18.4
9.0
12.0
14.1
18.4
14.1
18.4
14.1
18.4
34
MINIMUM
MAXIMUM
MAXIMUM
WIRE
WIRE
FUSE OR CKT
SIZE
LENGTH
AWG
FT (M)}
14
30 (9.4)
12
31 (9.5)
14
30 (9.4)
12
31 (9.5)
12
31 (9.5)
12
31 (9.5)
A11401
BKR
AMPS{
15
20
15
20
20
20