Carrier 59MN7B Installation, Start-Up, Operating And Service And Maintenance Instructions page 17

Modulating 4-way multipoise condensing gas furnace
Table of Contents

Advertisement

16. Open the spring clamp and insert the long end of the
adapter or the 1/2- -in. CPVC pipe into the outlet stub on the
drain tube.
17. Connect additional condensate piping to a code-approved
drain, or to a condensate pump approved for use with acidic
furnace condensate and compatible with mineral and
vegetable oils, such as canola oil.
Allow at least 1/4-in. per foot (20 mm per meter) of slope down
and away from the furnace in horizontal sections of drain line.
NOTICE
The field- -supplied, accessory horizontal drain trap grommet is
ONLY REQUIRED FOR DIRECT VENT APPLICATIONS.
It is NOT required for applications using single- -pipe or
ventilated combustion air venting.
TIP FROM CONTRACTORS: When installing the furnace
horizontally, use the entire drain elbow (that is, do NOT cut as
shown in Fig. 14 to connect the trap to the drain line. This helps
to prevent bumps and shocks to the drain line from damaging the
furnace drain trap. Avoid misalignment of the drain pipe which
may cause kinks in the elbow.
Horizontal Orientation
1. The condensate trap outlet extends 2- -in. (51 mm) below
the furnace casing. Leave enough clearance between the
furnace and the furnace platform for the trap.
2. To allow for servicing the trap, the condensate drain elbow
in the loose parts bag can be used to make a coupler to
allow for future service of the condensate trap and drain
line.
3. Remove the knock-out for the condensate trap in the side of
the casing.
4. Install the drain trap grommet in the casing if required for
direct- -vent applications. If necessary, remove the trap,
install the grommet and re-install the trap.
5. Remove the pre-formed rubber drain elbow, and two spring
clamps from the loose parts bag.
6. Connect the full or modified elbow and/or grommet to the
outlet of the condensate trap with one spring clamp. Avoid
misalignment of the drain pipe which may cause kinks in
the elbow or grommet.
7. The remaining drain line can be constructed from field- -
supplied 1/2- -in. CPVC or 3/4- -in. PVC
compliance with local building codes. A factory- -supplied
1/2- -in. CPVC to 3/4- -in. PVC adapter is supplied in the
loose parts bag for use as required.
8. Install the adapter or connect the 1/2- -in. CPVC pipe by
sliding a spring clamp over the open end of the elbow or
grommet on the outside the furnace casing.
9. Open the spring clamp and insert the long end of the
adapter or the 1/2- -in. CPVC pipe into the outlet stub on the
drain tube.
10. Connect additional condensate piping to a code- -approved
drain, or to a condensate pump approved for use with acidic
furnace condensate and compatible with mineral and
vegetable oils, such as canola oil.
Allow at least 1/4-in. per foot (20 mm per meter) of slope down
and away from the furnace in horizontal sections of drain line.
CAUTION
!
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care
and wear appropriate protective clothing, safety glasses and
gloves when handling parts, and servicing furnaces.
Fig. 15 - - Knockout Removal
17
pipe, in
L12F019B

Advertisement

Table of Contents
loading

Table of Contents