Technical Specifications

This section details the specifications and operating conditions of the device.
5.1

Power Supply Specifications

HI (125/250 VDC)
HI (110/230 VAC)
a
(F) denotes fast-acting fuse; (T) denotes time-delay fuse.
b
This is the same power supply for both AC and DC.
5.2

Failsafe Alarm Relay Specifications

Max Switching Volt-
age
Rated Switching Cur-
rent
5.3

Copper Ethernet Port Specifications

The following details the specifications for copper Ethernet ports that can be ordered
with the RUGGEDCOM RS400.
10/100Base-
a
Auto-negotiating.
b
Shielded or unshielded.
c
Auto-crossover and auto-polarity.
d
RMS 1 minute.
RUGGEDCOM RS400
Installation Manual, 02/2020, C79000-G8976-1016-10
Power Sup-
Minimum Input
ply Type
12-24 VDC
10 VDC
48 VDC
36 VDC
b
88 VDC
b
85 VAC
30 VAC, 80 VDC, 125 VAC, 250 VAC
0.3 A @ 30 VAC
1 A @ 30 VDC, 0.3 A @ 80 VDC
0.2 A @ 250 VAC
0.6 A @ 125 VAC
a
Speed
Connector
RJ45
TX
Maximum Input
36 VDC
59 VDC
300 VDC
265 VAC
Cable
a
Duplex
Wiring Standard
b
Type
FDX/HDX
> CAT-5
TIA/EIA T568A/B
Internal
Maximum Power
Fuse Rating
Consumption
a
6.3 A(F)
a
2 A(T)
8 W
a b
2 A(T)
Maximum
c
Distance
100 m (328 ft)
5
Isola-
d
tion
1.5 kV
27