IBM 5594-1AX Installation And User Manual page 32

Ibm 2u rack or tower ups rt1.5kva, rt2.2kva, and rt3.0kva
Table of Contents

Advertisement

16
Installation and User's Guide
Table 1. User settings (continued)
Submenu
On/Off settings
Cold start
Forced reboot
Auto restart
Energy saving
Sleep mode
Remote command
Available settings
Default settings
[Enabled] [Disabled]
[Enabled]
Authorize the unit to
start on battery
power.
[Enabled] [Disabled]
[Enabled]
If mains recover
during a shutdown
sequence:
If set to Enable,
shutdown sequence
will complete and
wait 10 seconds prior
to restart, if set to
Disable, shutdown
sequence will not
complete and restart
will occur
immediately.
[Enabled] [Disabled]
[Enabled]
Authorize the unit to
restart automatically
when mains recover
after a complete
battery discharge.
[Enabled] [Disabled]
[Disabled]
If Enabled, UPS will
shut down after 5
min. of back-up time,
if no load is detected
on the output.
[Enabled] [Disabled]
[Disabled]
If Disabled, LCD and
communication will
turn OFF
immediately after
UPS is OFF.
If Enabled, LCD and
communication stays
ON 1h30 min. after
UPS is OFF.
[Enabled] [Disabled]
[Enabled]
If Enabled, shutdown
or restart commands
from software are
authorized.