IBM 5594-1AX Installation And User Manual page 30

Ibm 2u rack or tower ups rt1.5kva, rt2.2kva, and rt3.0kva
Table of Contents

Advertisement

14
Installation and User's Guide
Table 1. User settings (continued)
Submenu
In/Out settings
Output voltage
Input thresholds
Sensitivity
Available settings
Default settings
Low voltage: [100 V]
Low Voltage model:
[120 V] [125 V]
110 V
High voltage: [200 V]
High Voltage model:
[208 V] [220 V] [230
230 V
V] [240 V]
User selectable when
UPS is powered for
the first time.
[Normal mode]
[Normal mode]
[Extended mode]
Extended mode
authorizes lower
input voltage (70 V)
without transferring
to battery. This can
be used if the load
can withstand low
voltage supply.
[High]
[High] [Low]
High: for sensitive
equipment, UPS will
easily transfer to
battery when utility
conditions are
becoming bad.
Low: for equipment
that can withstand
bad utility
conditions, in that
case, the UPS will
not transfer to
battery.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents