Siemens SITRANS RD500 Manual page 9

Configuring sitrans rd500 for connection to multiranger with modbus rtu
Hide thumbs Also See for SITRANS RD500:
Table of Contents

Advertisement

5. Enter the MODBUS start address for Reading (401010) with 1 Element and Read Only
access, and then click on Apply. (Another Address entry will appear below the first one.)
6. Click on Configure for the first address entry. The following screen will appear.
7. Enter a Tag for the reading and set the remaining parameters as in the image above, and
then click on Apply.
– Before DP – number of digits before the decimal place.
– After DP – number of digits after the decimal place.
– Be sure to select your previously enabled data log to begin logging the MultiRanger.
– If a value should be logged, but not displayed on the Overview screen, set View to No.
– Sign is register specific.
8. Click on Back to return to the list of tags.
Configuring SITRANS RD500 for connection to MultiRanger with MODBUS RTU
Application examples, 09/2020, AG111710
3.3 Configuring RD500 to Read MODBUS Registers from MultiRanger
Planning/configuring
9

Advertisement