Valve Linkages; Wiring Box - Honeywell M9484 Manual

Table of Contents

Advertisement

4.
Do not exceed the motor ratings in any installation.
5. Do not turn motor shaft manually or with a wrench-
this will damage the motor.

VALVE LINKAGES

The 220738A Mounting Bracket must be used with the
Q601 and Q618 linkages in all valve applications.
WIRING
Disconnect power supply before wiring to prevent electri-
cal shock or equipment damage. All wiring must agree with
applicable codes, ordinances, and regulations.
A transformer is required to supply 24 Vat power to the
motor. Make sure that the power requirements stamped on
the motor correspond to the characteristics of the power
supply.
MACHINE SCREWS OR BOLTS.
LTS SECURING BRACKET TO LINKAGE.
TIGHTEN AFTER SECURING MOTOR TO THE BRACKET USING FOUR BOLTS PROVIDED.
FIG. 4-MOTOR MOUNTING ON VALVE LINKAGE,.
Figs. 5 and 6 show internal schematics.
The motor terminals are quick-connects located on top
of theprintedcircuit boardshown in Fig.7.Ascrewterminal
adapter is standard on all Trade models and also may be
added to all models. Access to the wiring compartment is
gained byremovingthe4screws inthetoppf the wiring box
and lifting off the cover.

WIRING BOX

When used with liquid-tight conduit connectors, the wiring
box provides NEMA 3 weather protection for the motor.
The box also provides knockouts for wiring conduits and
encloses terminals. The wiring box, standard with replace-
ment motors, is required for housing an internal trans-
former, internal auxiliary switches or Series 70 Interface
Modules.
6
WIRING BOX
MOTOR

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

M9481M9494M9491

Table of Contents