Honeywell Modutrol IV Motors Series 90 Product Data

Honeywell Modutrol IV Motors Series 90 Product Data

Honeywell modutrol iv motors product manual

Advertisement

APPLICATION
The Series 90 Modutrol IV™ Motors are spring return and
non-spring return modulating proportional control motors. Use
these motors with controllers that provide a Series 90 output
to operate dampers or valves.
® U.S. Registered Trademark
Copyright © 2002 Honeywell • All Rights Reserved
Modutrol IV™ Motors
FEATURES
• Directly replaces M934A,D, M941, M944A,C,D,
M945A,D,F, M954, M965, and M975 motors.
• Oil-immersed motor and gear train for reliable
performance and long life.
• Integral junction box provides NEMA 3 weather
protection.
• Motor and circuitry operate from 24 Vac. Models
available with factory installed transformer, or a
field-added internal transformer.
• Quick-connect terminals standard—screw terminal
adapter available.
• Adapter bracket for matching shaft height of older
motors standard with TRADELINE motors.
• Field adjustable stroke (90° to 160°) models available.
• Nominal timing of 30 seconds for 90° stroke and 60
seconds for 160° stroke standard. Other timings
available.
• Die-cast aluminum housing.
• Integral auxiliary switches available factory mounted,
or can be field added to TRADELINE
• Integral spring returns motor shaft to normal position
(fully open or fully closed, depending on model) upon
power interruption.
• Field addable interface modules can be mounted in the
junction box to upgrade the motor to Series 70
(electronic) control.
• TRADELINE spring return motors can operate valve
linkages from power end or auxiliary end shafts for
normally closed or normally open valve applications.
Application ........................................................................
Features ...........................................................................
Specifications ...................................................................
Ordering Information ........................................................
Installation ........................................................................
Settings and Adjustments .................................................
Operation .......................................................................... 10
Replacement .................................................................... 12
®
Series 90
PRODUCT DATA
®
models.
Contents
1
1
2
2
5
8
63-2190-3

Advertisement

Table of Contents
loading

Summary of Contents for Honeywell Modutrol IV Motors Series 90

  • Page 1 Use these motors with controllers that provide a Series 90 output to operate dampers or valves. ® U.S. Registered Trademark Copyright © 2002 Honeywell • All Rights Reserved Series 90 Modutrol IV™ Motors FEATURES •...
  • Page 2: Series

    Honeywell, 1885 Douglas Drive North Minneapolis, Minnesota 55422-4386 In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Scarborough, Ontario M1V 4Z9. International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
  • Page 3 Controls, (918) 641-7381 or (918) 641-7374; or write to: O-Z/Gedney, Nelson Enclosures and Controls P.O. Box 471650 Tulsa, OK 74147-1650 Requires Honeywell 7617DM Coupling. Q100 Linkage connects Modutrol Valve. Requires the 220738A adapter bracket (packed with TRADELINE Modutrol IV motors).
  • Page 4: Power Consumption

    SERIES 90 MODUTROL IV™ MOTORS TOP VIEW 4-1/16 (103) 4-1/16 (103) 1-1/2 (37) AUXILARY 9/16 (15) ADAPTER BRACKET Fig. 1. Modutrol IV Motor mounting dimensions in inches (mm). Table 3. Series 90 Modutrol Motor Power Consumption Ratings. Non-Spring Return Motors 150 and 300 lb-in.
  • Page 5: Installation

    Table 5. Series 90 Modutrol Motor Timing and Torque Ratings. Nominal Timing in sec 90° 160° Spring Return 25 (2.8) 60 (6.8) — — Timings apply to all TRADELINE models. Some OEM models are available with non-standard timing/torque. The torque rating for dual-ended shaft motors is the sum of the shaft torques (power-end torque plus auxiliary-end torque). Breakaway torque is maximum torque available to overcome occasional large loads such as a seized damper or valve.
  • Page 6 SERIES 90 MODUTROL IV™ MOTORS Adapter Bracket The 220738A Adapter Bracket, positioned between the motor and the equipment, raises motor shaft height by 0.75 in. (19 mm) to match that of the former Modutrol The following applications require this bracket: •...
  • Page 7 STANDARD BOLTS (4) ADAPTER BRACKET EQUIPMENT BASE 1 #12 OR 1/4" ZINC PLATED MACHINE SCREWS OR BOLTS NON-SPRING RETURN M452E Fig. 3. Mounting the motor with an adapter bracket. Q5001 VALVE LINKAGE Fig. 4. Mounting the motor on a Q5001 Valve Linkage. SERIES 90 MODUTROL IV™...
  • Page 8: Settings And Adjustments

    SERIES 90 MODUTROL IV™ MOTORS SETTINGS AND ADJUSTMENTS Before Setting Stroke 1. Remove the top cover from the motor. 2. Disconnect the controller from the motor. 3. Connect a potentiometer to the motor as shown in Fig. 7. IMPORTANT Detach linkage from motor before adjusting stroke. Setting Stroke On adjustable stroke motors, stroke is field-adjustable between 90°...
  • Page 9 SERIES 90 MOTOR CONTROLLER TRANSFORMER (HOT) POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. TRANSFORMER MAY BE INTERNAL OR EXTERNAL Fig. 6. Typical Series 90 wiring. 135 Ohm MOTOR Potentiometer TRANSFORMER (HOT) POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
  • Page 10: Operation

    SERIES 90 MODUTROL IV™ MOTORS Auxiliary Switch Adjustment 1. Remove the top cover from the motor to gain access to the motor terminals and auxiliary cams. 2. Disconnect the controller from the motor. 3. Connect a potentiometer to the motor as shown in Fig. 7. 4.
  • Page 11 1/8 INCH STRAIGHT-BLADE SCREWDRIVER SLOW RISE PORTION INNER (APPROX. AUXILIARY 10 DIFF.) (RED) LEFT/OUTER AUXILIARY SWITCH SLOW RISE OUTER FAST RISE AUXILIARY PORTION (APPROX. 1 DIFF.) (RED) MOTOR MOTOR CLOSE OPEN POWER 1/8 INCH RIGHT/INNER STRAIGHT-BLADE AUXILIARY SCREWDRIVER SWITCH SLOW RISE PORTION INNER FAST RISE...
  • Page 12: Replacement

    220738A to raise the motor shaft to the appropriate height. Valve applications with a Q5001 Linkage do not require the 220738A Adapter Bracket. To operate Honeywell V5011 two- way or V5013 three-way valves through full stroke, use a 160° stroke motor.

Table of Contents