TRI-DUAL (TRI-D)

DEVICE PROGRAMMING UNIT USER'S MANUAL
If the settings are correct, press PROGRAM to
program the TRI. If label printing is selected, up to
nine labels will be printed. If the TRI is programmed
correctly, the display will appear similar to the
following:
TRI
AL
NO
LOOP=012
ADDRESS=41
PROGRAMMED OK
<EXIT
Press EXIT to return to the Main Menu. Use the
CHANGE button to go back and change a setting.
If the TRI was not programmed correctly, the display
will appear similar to the following:
TRI
AL
NO
LOOP=012
ADDRESS=41
PROGRAMMING FAILED
<EXIT
Press EXIT to return to the Main Menu. Press RE-DO
to reprogram the detector.
If the TRI was programmed correctly and the device
is removed, the "searching" screen will display.
TRIs must be programmed using cable P/N 555-133891
that is stored in the cable compartment in the bottom of
the DPU. Before starting to program TRIs, open the cable
compartment and insert the programming plug in one
end of the cable into the red and black banana jacks in
the cable compartment of the unit. (Refer to Figure 2,
pages 10-11.) Then follow the procedure below:
With the DPU displaying the Main Menu, press the
PROGRAM button. The DPU will prompt the user to
insert or connect a device or detector.
CHANGE>
RE-DO>
PROGRAMMING
17