DEVICE PROGRAMMING UNIT USER'S MANUAL
FC20 (FC2025, FC2050, FC2005, FC922, FC924, FC901) MANUAL TEST
FOR FDOOTC441/OOHC941
34
TESTING
Manual testing of the FDOOTC441/OOHC941 will
retrieve and display diagnostic information in a series of
four screens instead of the three-screen display for all of
the other devices. The fourth screen provides the CO
status of the detector. An example of a manual test for
the FDOOTC441/OOHC941 follows with a description of
the diagnostic information given in Table 4. The NEXT
button may be used to page to the next screen of
information.
FDOOTC441/OOHC941
ADDRESS=022
NORMAL
<EXIT
FDOOTC441/OOHC941 or FDOOT441
Example Screen 1
S/N=0494AB4
USAGE1=MULTI
USAGE2=THERMAL
<EXIT
FDOOTC441/OOHC941 or FDOOT441
Example Screen 2
IEC=CLEAN
TEMP=23C74F
SENS=3.14%/FT
<EXIT
FDOOTC441/OOHC941 or FDOOT441
Example Screen 3
CO=NORMAL
COC=50PPM
LIMIT=CO LEVEL
<EXIT
FDOOTC441/OOHC941 Example Screen 4
|
NEXT>
2
5
NEXT>
NEXT>
EXPIRING
NEXT>