DEVICE PROGRAMMING UNIT USER'S MANUAL
FC20 (FC2025, FC2050, FC2005, FC922, FC924, FC901) MANUAL TEST
FOR FDCIO422
36
TESTING
Manual testing of the FDCIO422 will retrieve and display
diagnostic information in a series of three screens. The
FDCIO422 three-screen display differs from the displays
of the other devices because the FDCIO422 can have
four usage settings. The input channel status is displayed
as "NORMAL " for Usage1 and Usage2 in Example
Screen 2. Screen 3 shows the input channel status as
"NORMAL " for Usage3 and Usage4.
An example of a manual test for the FDCIO422 follows
with a description of the diagnostic information given in
Table 5.
FDCIO422
ADDRESS=036
S/N=2F0494AB6
<EXIT
FDCIO422 Example Screen 1
NORMAL
USAGE1=ALARM
USAGE2=SUPV
<EXIT
FDCIO422 Example Screen 2
NORMAL
USAGE3=CL_A EOL
USAGE4=
CL_A EOL
<EXIT
FDCIO422 Example Screen 3
|
NORMAL
NEXT>
NORMAL
NC
NO
NEXT>
NORMAL
NC
NO
NEXT>
CHAPTER 3