Programming; Firefinder-Xls, Fs-250 And Fc20; Fc924 And Fc901) Detectors And Devices - Siemens DPU User Manual

Device programming unit
Table of Contents

Advertisement

2

Programming

FireFinder-XLS, FS-250 and FC20 (FC2025, FC2050, FC2005, FC922, FC924
and FC901) Detectors and Devices
The DPU will operate differently when programming detec-
tors and devices depending on which system is selected.
When programming devices for FC2025, FC2050, FC2005, FC922,
FC924 or FC901 panels, select the FC20 mode.
In FireFinder-XLS, FS-250 and FC20 (FC2025, FC2050,
FC2005, FC922, FC924 and FC901) systems, the DPU is
used only to set the address of detectors or devices. The
other configuration data such as ASD settings, usage, and
the type of the inputs on HTRIs, are sent from the
applicable panel's programming tool.
Refer to Figure 2 on pages 10-11 to connect the
device to be programmed.
At the Main Menu press PROGRAM. The display
will be a screen similar to the following:
PROGRAM P2 DEVICE
LOOP=012 ADDRESS=111
<LOOP
<EXIT
Press LOOP . The cursor will appear under the loop
number allowing the user the option to change the
loop setting by using the numerical keypad.
The loop number on the XLS is limited to 251; the
loop number on the FC2025, FC2050, FC922,
FC924 is limited to 64; the FS-250, FC2005 and
FC901 loop number is fixed at 1. Device addresses for
ADDRESS>
PROGRAM>
PROGRAMMING
9