Omron E5ZE-8 E Series Manual page 4

Multi-point temperature controller
Table of Contents

Advertisement

E5ZE-8j-E
J CHARACTERISTICS
Measurement precision
Adjustable sensitivity
Cooling coefficient
Proportional band
Integral time
Derivative time
Control cycle
Sampling cycle
Dead band/overlap Band
Alarm set range
Fuzzy logic strength
Fuzzy logic scale 1
Fuzzy logic scale 2
SV protection
SV protection time
Insulation resistance
Dielectric strength
Vibration resistance
Shock resistance
Enclosure rating
Weight
EMC
Approved standards
Note: 1. The measurement accuracy of the E5ZE used with a thermocouple B at 400°C or 750°F max. is not guaranteed. The following
measurement accuracy values are applied to the E5ZE.
K and T at –100°C max. and U:
K and T at –100°F max. and U:
R, S, and W at 200°C max., and B at 1,000°C max.:
R, S, and W at 400°F max., and B at 1,800°F max.:
2. The measurement accuracy of the E5ZE used with any thermocouple is 1°C/°F. The thermocouple can be used under the fol-
lowing temperature ranges to increase the measurement accuracy to as high as 0.1°C/°F.
K thermocouple:
T or U thermocouple:
N thermocouple:
J, E, L, or PLII thermocouple: Any temperature
3. To ensure EMC conformance, refer to Wiring for Conformance to the EMC Directives at the end of this data sheet.
216
Thermocouple:
(±0.3% of the measured value or ±2°C, whichever is larger) ±1 digit max.
(±0.3% of the measured value or ±3.6°F, whichever is larger) ±1 digit max.
Platinum resistance thermometer:
(±0.3% of the measured value or ±0.8°C, whichever is larger) ±1 digit max.
(±0.3% of the measured value or ±1.5°F, whichever is larger) ±1 digit max.
0.0°C to 99.9°C or 0.0°F to 99.9°F (0.1° increments), valid for ON/OFF control only.
0.0 to 10.0 (0.1 increments)
0.0°C to 999.9°C or 0.0°F to 999.9°F (0.1° increments)
Cooling: cooling coefficient × proportional band
0 to 3,999 s (1-s increments)
0 to 3,999 s (1-s increments)
Heating or cooling: 1 to 99 s (1-s increments)
Approx. 200 ms/8 control points
–999 ° to 999° (1° C or F increments)
With 1° increments: –999° to 9,999° (0° to 9,999° with upper/lower limit alarms)
With 0.1° increments: –999.9° to 9,999.9° (0.0° to 9,999.9° with upper/lower limit alarms)
0 to 99% (1% increments)
0.2° to 999.9° (0.1° C or F increments)
0.02° to 99.99° (0.01° C or F increments)
Lithium battery backup
10 years min. at room temperature
20 MΩ at 500 VDC between the FG terminal and analog input terminals
Leakage current of 1 mA max. between the FG terminal and analog input terminals when 500 VAC
is applied for 1 min.
Malfunction: 10 to 55 Hz with 15 m/s
Destruction: 10 to 55 Hz with 20 m/s
(15.3G) max. 3 times each in ±X, ±Y, and ±Z directions
2
Malfunction: 150 m/s
(20.4G) max. 3 times each in ±X, ±Y, and ±Z directions
2
Destruction: 200 m/s
IP00
Enclosed Unit: 1,700 g max.
Open frame: 900 g max.
Emission Enclosure
Immunity ESD:
Immunity RF-interference:
Immunity conducted disturbance: ENV50141:
Immunity burst:
Conforms to EN50081-2, EN50082-2 (See Note 3)
±3°C ±1 digit max.
±5.4°F ±1 digit max.
0.0 °C to 1,300.0 °C, 0.0 °F to 2,300.0 °F
0.0 °C to 400.0 °C, 0.0 °F to 700.0 °F
400.0 °C to 1,300.0 °C, 700.0 °F to 2,300.0 °F
2
(1G) for 10 minutes each in X, Y, and Z directions
2
(2G) for 2 hours each in X, Y, and Z directions
EN55011 Group1 class A
EN61000-4-2:
4 kV contact discharge (level 2)
8 kV air discharge (level 3)
ENV50140:
10 V/M amplitude modulated,
80 MHz to 1 GHz (level 3)
10 V/m (pulse modulated, 900 MHz)
10 V (0.15 to 80 MHz) level 30)
EN61000–4–4:
2 kV power line (level 3)
±4°C ±1 digit max.
±7.2°F ±1 digit max.
E5ZE-8j-E