Omron E5ZE-8 E Series Manual page 16

Multi-point temperature controller
Table of Contents

Advertisement

E5ZE-8j-E
J WIRING FOR CONFORMANCE TO THE EMC DIRECTIVES
Thermocouple Input Model
Communications cable
Setting display unit
Outside the control panel
Inside the control panel
Platinum Resistance Thermometer Input Model
Setting display unit
Outside the control panel
Inside the control panel
Note: 1. Place the power supply, filter, input sensor, I/O terminals, and communications cable inside the control panel when wiring them.
2. If the communications cable between devices extends outside the control panel, satisfy the following conditions when wiring
them.
Use shielded cables for communications cables and ground to the FG.
Insert at least five ferrite cores close to the E5ZE.
228
PLC
Power supply
Filter
I/O terminals
E5ZE-CBLj00
Ferrite core: ZCAT2032 by TDK
Filter: MBS-1210-22 by Nemic Lambda
PLC
Communications cable
Power supply
I/O terminals
E5ZE-CBLj00
E5ZE
or
24 VDC
Ferrite core
Alarm output
Control output
CT input
Thermocouple input
FG
E5ZE
or
24 VDC
Alarm output
Control output
CT input
Platinum resistance
thermometer input
FG
E5ZE-8j-E
c:/H75E11+H61E11