NCA Connections
C.5 NCA Connections
The NCA does not provide an annunciator power output terminal. Power for the LDM should be drawn from the FACP's main
Power
power supply. Refer to the appropriate FACP appendix in this manual.
EIA-485
C.6 AM2020/AFP1010 Connections
Connect the power run for the LDMs to MPS-24A TB3, Terminals 1 (+) and 2 (-). Maximum current is 1 amp. The power run to
Power
the LDMs need not contain a Power Supervision Relay since loss of power is inherently supervised.
EIA-485: AM2020/AFP1010 Hardware Required
2048A) or SIB-NET. The EIA-485 circuit must be connected to the SIB-2048A as illustrated below.
The SIB-2048A can support one EIA-485 circuit, capable of spanning 12,000 feet (3,600 m) @ 12 AWG (3.25 mm2), as illustrated
below, provided that the SIB-2048A is located in the center of the span illustrated below. A 120 ohm terminating resistor is required at
each end of the twisted pair.
LDM Series Instruction Manual — P/N 15885:H3 8/12/2019
NFS2-3030 and NCA-2 (UL 9th), AM2020/AFP1010, NFS-3030, or NCA (UL 8th)
24 VDC Power (+) TB3-1
TB1
EARTH GND
AC NEUTRAL
AC HOT
CB1
The AM2020/AFP1010 must include an intelligent Serial Interface Board (SIB-
Supervised and Power-Limited
Figure C.1 The EIA-485 Loop
LDM-32
J5
J6
OU TPUTS J7
J8
J4
J11
+5 VDC
J10
LAMP
J9
POW ER
SW ITCH
MA TRIX
J1
SW 1
24V Power
J2
SW 2
SW3
SW 4
TB2
7
6
5
4
TB1
3
2
1
ON LINE
EIA-485 Loop
LED
6,000 feet
Max (1,800 m)
R98 - ACS Bus Termination Resistor
Termination resistor built into board for NCA
installations at physical end of ACS Bus. If an
NCA is not installed at end of Bus, remove
resistor R98. Remove all AC and DC power
before cutting.
TB3 - EIA-485 ACS Mode Data connection
for ACS modules. Power limited and
unsupervised.
Common (-) TB3-2
PO WER LIMITED
BA T +
BA T -
+24R COMMON
+24
COMMON
TB2
F1
P3
MPS-24A
{
EIA-485 Common
Earth Ground (chassis)
EIA-485 Loop 1 (+)
EIA-485 Loop 1 (-)
EIA-485 Loop 2 (+)
EIA-485 Loop 2 (-)
Control Panel
24V Power
EIA-485 Loop
6,000 feet
Max (1,800 m)
P2
P5
P4
R27
P5
SIB-2048A
LDM-32
J5
J6
OUTPUTS J7
J8
J11
+5 VDC
J4
J10
LAMP
J9
PO WER
SW ITCH
MA TRIX
J1
SW 1
J2
SW 2
SW 3
SW 4
TB2
7
6
5
4
TB1
3
2
1
ON LINE
LED
45

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Notifier ldm-32Notifier ldm-e32

Table of Contents