3.7

Main Circuit Wiring

This section describes the functions, specifications, and procedures required to safely and properly wire the main circuit in
the drive.
NOTICE: Do not solder the ends of wire connections to the drive. Soldered wiring connections can loosen over time. Improper wiring practices
could result in drive malfunction due to loose terminal connections.
NOTICE: Do not switch the drive input to start or stop the motor. Frequently switching the drive on and off shortens the life of the DC bus
charge circuit and the DC bus capacitors, and can cause premature drive failures. For the full performance life, refrain from switching the
drive on and off more than once every 30 minutes.
Note:
Refer to Single-Phase Derating on page 329
Refer to Factory Recommended Branch Circuit Protection for UL Compliance on page 500
u
Factory Recommended Branch Circuit Protection
WARNING! Fire Hazard. Install adequate branch circuit protection according to applicable local codes and this manual. Failure to comply
could result in fire and damage to the drive or injury to personnel. The device is suitable for use on a circuit capable of delivering not more
than 100,000 RMS symmetrical amperes, 240 Vac (200 V class) and 480 Vac (400 V class), when protected by branch circuit protection
devices specified in this manual.
Branch circuit protection shall be provided by any of the following: Non-time delay Class J, T, or CC fuses sized at 300% of the drive input
rating, or Time delay Class J, T, or CC fuses sized at 175% of the drive input rating, or MCCB sized at 200% maximum of the drive input
rating.
Yaskawa recommends installing branch circuit protection according to maintain compliance with UL508C. Semiconductor
protective type fuses are preferred. Alternate branch circuit protection devices are also listed in this manual.
Recommended Branch Circuit Protection on page 488
u
Main Circuit Terminal Functions
Terminal
200 V
Class
400 V
Drive Model
Class
600 V
Class
R/L1
S/L2
T/L3
R1-L11
S1-L21
T1-L31
U/T1
V/T2
W/T3
B1
B2
⊕2
• DC link choke
connection
⊕1
(⊕1, ⊕2)
(remove the
shorting bar
between
⊕1 and ⊕2)
• DC power
supply input
(⊕1, ⊖)
⊕3
YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive - iQpump1000 User Manual
for applying and protecting the drive when using single-phase input power.
Table 3.1 Main Circuit Terminal Functions
2A0004 to
2A0110, 2A0138
2A0081
4A0002 to
4A0058, 4A0072
4A0044
5A0003 to
5A0041, 5A0052
5A0032
Main circuit power supply input
Not available
Drive output
Braking resistor
DC power supply
input
(⊕1, ⊖)
Not available
for details.
Type
2A0169 to
2A0415
4A0088 to
4A0930, 4A1200
4A0675
5A0062 to
5A0242
Main circuit power
supply input
Not available
Not available
• DC power supply input (⊕1, ⊖)
• Braking unit connection (⊕3, ⊖)
3.7 Main Circuit Wiring
for details on fuse selection.
Refer to Factory
Function
Connects line power to the
drive
Connects line power to the
drive
Remove the shorting bars
connecting R/L1-R1/L11,
S/L2-S1/L21, T/L3-T1/L31
when using 12-phase
rectification.
Connects to the motor
Available for connecting a
braking resistor or a braking
resistor unit option
For connecting:
• the drive to a DC power
supply
• dynamic braking options
• a DC link choke
Page
93
3
93
107