NOTE ON DRAINPIPE INSTALLATION
● When using an extended drainpipe, tighten
the indoor connection with an additional
protection tube to prevent it from pulling
loose.
● The drainpipe should slope downward at a
gradient of at least 1/100 to prevent water
from flowing back into the air conditioner.
● To prevent the pipe from sagging, space
hanging wires every 1-1.5m (39-59").
● If the outlet of the drainpipe is higher than
the body's pump joint, provide a lift pipe for
the exhaust outlet of the indoor unit. The lift
pipe must be installed no higher than 75cm
(29.5") or100cm (39.4") from the ceiling
board and the distance between the unit
and the lift pipe must be less than 30cm
(11.8") (depending on models ). Incorrect
installation could cause water to flow back
into the unit and flood.
● To prevent air bubbles, keep the drain hose
level or slightly tiled up (<75mm / 3") (some
models ).
(A)
Ceiling
≤ 30cm (11.8")
0 - 75mm
(3")
(B)
(A)
≥10cm
(4")
Pass the drain hose through the wall hole. Make
sure the water drains to a safe location where it will
not cause water damage or a slipping hazard.
1 - 1.5m
(39-59")
53cm
75cm
(20.8")
(29.5")
22cm
(8.6")
1 - 1.5m
(39-59")
≤100cm
(39.4")
NOTE: When connecting multiple drainpipes,
install the pipes as illustrated in the following
Figure.
0-53cm
(20.8")
(B)
Vent
NOTE: The drainpipe outlet should be at least
5cm (1.9") above the ground. If it touches the
ground, the unit may become blocked and
malfunction. If you discharge the water directly
into a sewer, make sure that the drain has a U or
S pipe to catch odors that might otherwise come
back into the house.
≤100cm
(39.4")
Page 12-GB