6.2 WORKING LIMITS OF HEAT PUMP

It's recommended to operate unit inside the working limits that are reported here below, in order to avoid any possible
intervention of the safety and protection devices.
In any case, as regards high temperatures for water, if the setting temperature is outside the operating region, the unit
will automatically adapt its set of the water temperature respecting the limits shown in the below diagram.
Here below the fixed sets of the pressure switches:
- HP switch: OFF=25 bar, ON=18 bar
- LP switch: OFF=0,2 bar, ON=1 bar.