7 APPLICATION FUNCTIONS

7.7 Simple Dual-Structured Network (High Performance model QCPU and Process CPU)

7 - 115
By installing two network modules, a regular network module and a standby network
module, to each CPU module, data linking can be continued by switching to link data
refreshing with the standby network when a faulty area is detected on the regular
network due to wire breakage, etc. When there is no error, both the regular and
standby network modules will be executing data linking at the same time.
POINT
A simple dual-structured system cannot be constructed with the Simple dual-
structured system cannot be configured with the Basic model QCPU, Redundant
CPU, and Universal model QCPU. These CPUs are applicable for a single network
system.
(1)
The switching between the regular and standby networks (i.e., which network the
CPU module refreshes) is performed by the sequence program.
By checking the data link status (SB0074, SW0074 to 0077) of each station, the
sequence program refreshes with the standby network modules when an error is
detected in the regular network.