Removing The Ex Baseunit For Ex Power Module - Siemens SIMATIC ET 200SP HA System Manual

Modules for devices in a hazardous area
Hide thumbs Also See for SIMATIC ET 200SP HA:
Table of Contents

Advertisement

Removal
7.2 Removing the Ex module group
Procedure
Step
1
3
7.2.6

Removing the Ex BaseUnit for Ex power module

Requirement
• All adjacent components on the right (Ex BaseUnit or server module) have been removed.
You can find information on this in the following sections:
– Section "Removing a server module (Page 72)"
– Section "Pull Ex I/O module (Page 73)"
– Section "Removing an Ex power module (Page 73)"
– Section "Removing the Ex BaseUnit for Ex I/O module (Page 75)"
• There is a clearance of at least 8 mm to adjacent Ex BaseUnits.
76
Procedure
Press the mounting rail release at the top of the Ex Base‐
Unit
and move the Ex BaseUnit at least 8 mm to the
right
.
1. Keep the mounting rail release on the Ex BaseUnit
pressed
and swing the Ex BaseUnit out of the
mounting rail
.
2. Lift the Ex BaseUnit upwards from the mounting
rail
.
Illustration
Modules for devices in a hazardous area
System Manual, 04/2021, A5E50165138-AA