Figure E-1
E.1.3

Diagnostic and maintenance messages

Diagnostic message
A diagnostic message is output for each diagnostic event, and the DIAG LED on the EX power
module flashes red.
The diagnostic messages can be read in the diagnostic buffer of the CPU.
Table E-2
Diagnostic messages, their meanings and remedy options
Diagnostic mes‐
Error code
sage
Parameter assign‐
10
ment error
Supply voltage miss‐
11
ing
Channel/component
1F
temporarily unavail‐
able
Invalid BaseUnit
151
The retentive memo‐
153
ry in the BaseUnit is
defective.
Maintenance message
Whenever it is detected that maintenance is required, a maintenance message is generated. The
MT LED lights up on the module. The messages have no direct effect on the function of the
module.  
Table E-3
Maintenance message, its meaning and remedies
Maintenance mes‐
Error code
sage
The retentive memo‐
153
ry in the BaseUnit is
defective.
E.1.4

Address space

The Ex power module does not use any data in the input or output data area.
Modules for devices in a hazardous area
System Manual, 04/2021, A5E50165138-AA
Header information and module parameters data record 128 of the Ex PM-E Ex power
module
Assign‐
Meaning
ment
Module
Incorrect parameter assignment
H
Module
Missing or insufficient supply volt‐
H
age L+
Module
Firmware update is in progress or has
H
been canceled during the update.
Module
The module was plugged into an im‐
H
permissible Ex BaseUnit.
Module
A memory block error on the Ex Base‐
H
Unit was detected during startup.
Assign‐
Meaning
ment
Module
A memory block error on the Ex Base‐
H
Unit was detected during operation.
Drivers, parameters, diagnostic messages and address space
E.1 Address space for the Ex power module
Remedy
Correct the parameter assignment
Check supply voltage L+ and wiring
on the Ex power module
Restart the firmware update
Wait for firmware update
Replace Ex BaseUnit
Replace Ex BaseUnit
Remedy
Replace Ex BaseUnit