Figure  3.8 Flow  Chart  For  Setpoint  Deviation/Field  Calibration - Omega i Series User Manual

Temperature/process limit controller
Hide thumbs Also See for i Series:
Table of Contents

Advertisement

3.2.9  Setpoint  Deviation  Menu  /  Field  Calibration  (continued)
ENTER  READING  ADJUST  MENU:
Press  d
Press  b
Press  d
Setpoint  Deviation  menu,  if  "enabled",  allows  changes  to  Setpoint  1  to  be  
made  automatically  to  Setpoint  2.  This  mode  is  very  helpful  if  the  Process  value  
changes  often.  
In  Setpoint  Deviation  Mode,  set  SP2  a  certain  number  of  degrees  or  counts  away  
from  SP1  -­  this  relation  remains  fixed  when  SP1  is  changed.  
For  instance:  Setting  SP1=200  and  SP2=20  and  enabling   SP.DV  means  that  the  
absolute  value  of  SP2=220.  
Moving  SP1  to  300,  the  absolute  value  of  SP2  becomes  320.
THERMOCOUPLE  FIELD  CALIBRATION  SUBMENU:
CAUTION:  Do  not  perform  the  following  steps  until  you  fully
understand  this  entire  section.
RTD  and  Process  are  perfectly  calibrated.  This  section  is  applicable  to  
Thermocouple  (TC)  calibration  only.
Be  sure  that  the  TC  being  used  to  calibrate  the  meter  is  of  the  type  
selected  in  the  TC  submenu.  Place  the  TC  in  an  ice-­bath  (or  other  0°C  /  
32°F  environment).  In  ambient  temperature  conditions:  connect  the  TC  
to  the  meter,  apply  power  to  the  meter.
CAUTION:  Do  not  proceed  with  TC  calibration  unless  the  above  
conditions  have  been  in  effect  for  at  least  one  hour.
Press  d
Press  b
Press  d *
Press  d *
re-­press  the  last  button  you  pressed,  to  avoid  unintentionally  mis-­
calibrating  your  meter.
4)  Display  advances  to  Setpoint  Deviation   ENBL  Enable  or  
DSBL .  Disable  Submenu  and  flashes  the  previous  selection.
5)  Scroll  through  the  available  selections:   ENBL  or   DSBL .
6)  Display  shows   STRD  stored  message  momentarily  and  then
advances  to  the  next  menu  item.
7)  Display  shows   CAL1  .
8)  Display  shows  flashing   0000 .
9)  Display  will  still  show  flashing   0000 .
10)  Display  shows   OUT1  (meaning  Calibration  is  complete)