H42 Rear Venting Graph - Montigo DIVINE H34DFN Installation & Maintenance Manual

Divine single sided indoor direct vent gas fireplace
Table of Contents

Advertisement

If the 'X' falls on or above the top boundary of the shaded area, the
installation is acceptable.
Selection of components and details of venting layout should adhere
to the following guidelines:
Vent terminations must not be recessed in walls or siding.
For Heat Shield requirements see Section 3-3.
Once the proposed venting layout has been determined refer to
graph to ensure the layout is acceptable.
Notes Wall Mounted Terminations: REAR VENT
All measurements for vertical or horizontal runs are measured from
center of the vent pipe.
Venting runs must fall within the limits set by the venting graph.
If the vertical dimension from the hearth is 120" and the horizontal
acceptable installation.
If the vertical dimension from the hearth is 48" and the horizontal run
acceptable installation.
would not be an acceptable installation.
REAR VENT RUN
132
120
within non-shaded area.
96
72
60
36
12
0
0
12
36
60
Horizontal Run (In.)
Figure 8.l
A
C
B
within shaded area.
72
96
120
132
156
18'' Max. horozontal
run with no vertical lift
Hearth
Figure 8.m
Flex or Rigid
Hearth
Figure 8.n
Installation
PXT Extention
Heat Sheild
Termination
18''
33''
Max.
Max.
30''
Max.
19''
Min.
52''
Min.
18''
Max.
33"
XG0228 - 021419
-