Technical Specifications

This section provides important technical specifications related to the device.
5.1

Power Supply Specifications

Note
When determining cable lengths, make sure the minimum input voltage for the
power supply is provided at the power source.
Supply Type
a
Power consumption varies based on the device configuration.
b
(T) denotes time-delay fuse.
5.2

Failsafe Relay Specifications

Maximum Switching Voltage
a
Inductive load R/L = 7 ms
b
Resistive load
RUGGEDCOM RX1536
Installation Manual, 04/2021, C79000-G8976-1488-02
Input Range
Power
Min
88 VDC
HI
85 VAC
88 VDC
HIP
85 VAC
24
13 VDC
24P
48
36 VDC
48P
12
9 VDC
12P
30 VDC
125 VDC
250 VAC
Internal
Fuse Rating
Max
300 VDC
3.15 A(T)
264 VAC
300 VDC
3.15 A(T)
264 VAC
b
36 VDC
10 A(T)
72 VDC
3.15 A(T)
15 VDC
12 A
Rated Switching Current
5 A
a
b
0.1 A
, 0.15 A
6.25 A
Maximum
Power
Insulation
a
Consumption
b
65 W
2800 VDC
for 1 minute
b
65 W
63.5 W
1500 VDC
for 1 minute
b
60 W
1500 VAC or
67 W
2121 VDC
for 1 minute
Isolation
2800 VDC for 1 minute
between coil and contacts
5
43