SmartLinx PROFIBUS DP-V1
Operating Instructions
Edition
08/2015

Advertisement

Table of Contents
loading

Summary of Contents for Siemens PROFIBUS DP-V1

  • Page 1 Communication SmartLinx PROFIBUS DP-V1 Operating Instructions Edition 08/2015...
  • Page 2 76181 Karlsruhe Peterborough, Ontario, Canada, K9J 7B1 Deutschland Email: techpubs.smpi@siemens.com • For a selection of Siemens level measurement manuals, go to: Level www. siemens.com/processautomation. Under Process Instrumentation, select Measurement and then go to the manual archive listed under the product family.
  • Page 3: Table Of Contents

    Table of contents Safety notes ............................1 The Manual .............................1 Technical support ..........................2 Product feedback...........................2 SmartLinx PROFIBUS DP-V1 ....................3 Specifications ........................4 Installation........................... 5 Software............................5 Hardware ............................5 Cable connector .............................6 Termination switch ..........................6 Operation ..........................7 Operation LED ............................7 LED status indicators ..........................7 Error conditions of the red diagnostics light .................8...
  • Page 5: Safety Notes

    This manual will help you install and connect a Siemens SmartLinx PROFIBUS DP-V1 module, and set it up for communication with a master device on a PROFIBUS DP-V1 network. The manual is targeted at a technical audience in the industrial communications field with a sound working knowledge of PROFIBUS DP-V1.
  • Page 6: Technical Support

    Technical support Support is available 24 hours a day. To find your local Siemens Automation Office address, phone number and fax number go www.siemens.com/automation/partner • Click on the tab Contacts by Product then drill down to find your product group (+Process Automation >...
  • Page 7: Smartlinx Profibus Dp-V1

    MultiRanger 200 HMI or the HydroRanger 200 HMI (also referred to as Siemens device in this operating instructions) to any PROFIBUS DP network. However, to access the Acyclic data map, the master must support either DP-V1 or DP-V2.
  • Page 8: Specifications

    Baud rate: 9.6 Kbaud to 12 Mbaud, automatically detected. Termination Switch selectable, open or special active termination as per PROFIBUS specification (see Termination switch on page 6). Cable Belden PROFIBUS cable 3079A, or equivalent. Page 4 SmartLinx PROFIBUS DP-V1 – Operating Instructions A5E36197302...
  • Page 9: Installation

    Installation The SmartLinx module is either pre-installed in the Siemens device or shipped separately for on-site installation. Refer to the operating instructions of your Siemens device for details on module location and physical installation. Software Product Software revision MultiRanger 200 HMI 2.00...
  • Page 10: Cable Connector

    Switch position Open (not used) Line A Line B PROFIBUS DP-V1 requires termination of the bus at both end points. See the PROFIBUS DP-V1 specifications for details. The termination switch is not present on all modules. Page 6 SmartLinx PROFIBUS DP-V1 – Operating Instructions...
  • Page 11: Operation

    Operation Communication on the PROFIBUS DP-V1 link is indicated by the SmartLinx LEDs. Operation LED • Orange blinks as the module is initialized. • Green blinks during normal operation. LED status indicators Fieldbus Online Acyclic Traffic Fieldbus Fieldbus Offline Diagnostics...
  • Page 12: Error Conditions Of The Red Diagnostics Light

    See Configuring the slave device on page 10 for supported lengths. 4Hz – Error in initialization Consult your Siemens representative. Page 8 SmartLinx PROFIBUS DP-V1 – Operating Instructions A5E36197302...
  • Page 13: Communication Setup

    Communication setup The SmartLinx PROFIBUS DP-V1 module is a slave on the bus, and does not use any Siemens device parameters for configuration. Set the rotary switches on the module to the desired slave address. Other settings are provided in the GSD file or are automatically detected.
  • Page 14: Configuring The Slave Device

    After you import the GSD file, you can find the hardware in the hardware catalogue. If you are using Step 7, go to PROFIBUS DP-V1 > Additional Field Devices > General > Anybus- DPV1 IM.
  • Page 15: Module Identification

    Save and compile the hardware configuration and download to the PLC. Module identification The following parameters are used together for module identification. Please refer to the Parameters chapter of your Siemens device operating instructions for more details about the subject. 3.2.10.4. Smartlinx®Module Type (Read only) Identifies the module used.
  • Page 16: Application Layer

    This section describes the information that can be read and written to the MultiRanger 200 HMI or the HydroRanger 200 HMI. The PLC reads data from the Read block (PLC input) of the PROFIBUS DP-V1 module. Please note that the current firmware of the HydroRanger 200 HMI does not require a Write block (PLC output) to be configured in the PLC, as cyclic writing to the MultiRanger 200 HMI is not supported at this time.
  • Page 17 References the Totalizer parame- ter within the Siemens device. Word 2: PV Point 1 Status Profi status PV status byte. Hexadecimal Byte status number 0x80 Good 0x10 Bad: malfunction 0x1f Bad: out-of-service A5E36197302 SmartLinx PROFIBUS DP-V1 – Operating Instructions Page 13...
  • Page 18: Slot Index (Acyclic)

    The following table shows the slot and index assignments of the different elements (or parameters). The elements are numbered in the order that they are returned. Please see the Parameters chapter of your Siemens device operating instructions for details on the parameters used below.
  • Page 19 Pump by Rate (2.8. 1 .8.) - UINT8 2. Level Setpoint Variation (2.8.2.6.2.) - Float32 1 or 2 Flow Maximum (3.2.6. 1 5.) - Float32 2. Flow Minimum (3.2.6.16.) - Float32 A5E36197302 SmartLinx PROFIBUS DP-V1 – Operating Instructions Page 15...
  • Page 20 1 or 2 158-189 1. Head 1 (2.13.6.1.1.) - Float32 2. Flow 1 (2.13.6.1.2.) - Float32 Scan Time (2. 1 . 1 5.) - Float32 Level (3.2.6.3.) - Float32 2. mA Value Transducer - Float32 Page 16 SmartLinx PROFIBUS DP-V1 – Operating Instructions A5E36197302...
  • Page 21 3. ON Setpoint (2.8.1.5.) - Float32 Relay Logic (2.8.1.11.) - UINT8 4. OFF Setpoint (2.8. 1 .6.) - Float32 8. Relay Fail-safe (2.8.2.3.) - INT8 5. Relay Interval Setpoint (2.8.2.4.) - INT32 A5E36197302 SmartLinx PROFIBUS DP-V1 – Operating Instructions Page 17...
  • Page 22 9. Modem Inactivity Timeout 4. Serial Baud Rate (4.5.) - Float32 (4.10.) - UINT16 5. Parity (4.6.) - UINT8 Parameter Index Location (4.11.) - UINT16 79-80 Communications Control (5.4.) - INT16 Page 18 SmartLinx PROFIBUS DP-V1 – Operating Instructions A5E36197302...
  • Page 23 2. Convert Reading (2. 1 2.5.)- Float32 Tag (3.1.1.) - UINT8 4. Date Last Configured (3. 1 . 1 0.) - 2. Message (3. 1 .3.) - UINT8 UINT8 3. Descriptor (3.1.2.) - UINT8 A5E36197302 SmartLinx PROFIBUS DP-V1 – Operating Instructions Page 19...
  • Page 24: Data Types

    Data types The Siemens device parameters take on many values in various formats, as discussed in the Siemens device operating instructions. For the convenience of the programmer, those values are converted to and from 16-bit integer numbers, since those are easily handled by most PLCs.
  • Page 25: Split Values

    An example is Echo Confidence as shown in Measurement View 2 (see The LCD Display section of your Siemens device operating instructions). In this case, a pair of 8-bit unsigned integers are viewed as a single value.
  • Page 26 OPEN 30007 SHORT 30008 PASS 30009 FAIL 30010 HOLD 30011 30012 30013 30014 30015 Parameter has not been set. -32768 Value is less than –20,000 32767 Value is greater than 20,000 Page 22 SmartLinx PROFIBUS DP-V1 – Operating Instructions A5E36197302...
  • Page 27: Relay Function Codes ( 2.8.1.4. Relay Function Only)

    First In First Out (FIFO) First In First Out Flush Valve Flush Valve Control Communication Communication of your Siemens device operating instructions for full details 2.8. 1 .4. Relay Function about this parameter. A5E36197302 SmartLinx PROFIBUS DP-V1 – Operating Instructions Page 23...
  • Page 28: Troubleshooting

    Please contact your Siemens representative to get a software upgrade or to receive instructions. 3. Make sure the Siemens device is set to a unique address to prevent conflict with any other slave(s) on the bus. Check the configuration of the scanning master to make sure it is functioning properly.
  • Page 29: Index

    UINT32 (Unsigned 32-bit Integer). See Data Online 7 types. Floating point number. See Data types. GSD files 10 Hardware 5 Installation 5 Integer. See Data types. LED 7 Module identification 11 A5E36197302 SmartLinx PROFIBUS DP-V1 – Operating Instructions Page 25...
  • Page 32 For more information www.siemens.com/level www.siemens.com/weighing Siemens Canada Limited 1954 Technology Drive P.O. Box 4225 Printed in Canada Peterborough, ON Subject to change without prior notice Canada K9J 7B1 A5E356197302 Rev. AA email: techpubs.smpi@siemens.com © Siemens AG 2015 www.siemens.com/processautomation...