Siemens SIMATIC NET RUGGEDCOM RX1536 Installation Manual page 63

Rugged multi service platforms
Hide thumbs Also See for SIMATIC NET RUGGEDCOM RX1536:
Table of Contents

Advertisement

Certification
6.2 EMC and Environmental Type Tests
EMC Immunity Type Tests for IEEE 1613
Note
The RUGGEDCOM RX1536 meets Class 2 requirements for an all-fiber
configuration and Class 1 requirements for copper ports. Class 1 allows for
temporary communication loss, while Class 2 requires error-free and interrupted
communications.
Environmental Type Tests
54
Description
HV Impulse
Dielectric Strength
Fast Transient
Oscillatory
Radiated RFI
ESD
Test
IEC 60068-2-1
Cold Temperature
IEC 60068-2-2
IEC 60068-2-30
IEC 60068-2-78
Humidity (Damp Heat, Steady State)
IEC 60068-2-14
IEC 60255-21-1
IEC 60255-21-2
IEC 60255-21-3
Signal ports
DC Power Ports
AC Power Ports
Signal ports
DC Power Ports
AC Power Ports
Signal ports
DC Power Ports
AC Power Ports
Earth ground ports
Signal ports
DC Power Ports
AC Power Ports
Enclosure ports
Enclosure Contact
Enclosure Air
Description
Test Ad
Dry Heat
Test Bd
Humidity (Damp
Test Db
Heat, Cyclic)
Change of Temperature
Vibration
Shock
Bump
Seismic
Test Levels
5 kV (Failsafe Relay Output)
5 kV
2 kV
1.5 kV
2 kV
± 4 kV @ 2.5 kHz
± 4 kV
2.5 kV common mode @1MHz
2.5 kV common
1 kV differential mode @ 1 MHz
35 V/m
± 8 kV
± 15 kV
Test Levels
-40 °C (-40 °F), 16 Hours
85 °C (185 °F), 16 Hours
95% (non-condensing),
55 °C (131 °F), 6 cycles
10 days at 40 °C
(104 °F) and 93%
relative humidity
(non-condensing)
5 cycles at -40 to 85 °C
(-40 to 185 °F) and 3
hour dwells at rate of
1 °C/min (1.8 °F/min)
2 g @ 10-150 Hz
30 g @ 11 ms
10 g @ 16 ms
Method A
RUGGEDCOM RX1536
Installation Manual, 04/2021, C79000-G8976-1488-02
Severity
Levels
 
 
 
 
 
Class 2
Class 2
Class 1
Level 2

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simatic net ruggedcom rx1500Ruggedcom rx1536

Table of Contents