Installing the Device
2.5.1 Connecting High AC/DC Power
2.
3.
4.
5.
14
Negative/Neutral (-/N) Terminal
6
Figure 2.6
AC Terminal Block Wiring – Screw Terminal Block for HI Power Supplies
Note
For secure, reliable connections under severe shock or vibration, use M3.5 ring
lugs with a maximum outer diameter of 7 mm (0.28 in). Make sure no bare
metal is exposed beyond the safety cover.
Connect the positive wire from the power source to the positive/live (+/L)
terminal on the terminal block.
Connect the negative wire from the power source to the neutral/negative (-/N)
terminal on the terminal block.
For screw terminal blocks, install the safety cover.
Screw
1
Safety Cover
2
Screw Terminal Block
3
RUGGEDCOM RX1536 Device
4
Figure 2.7
Assembling the Safety Cover
Using a braided wire or other appropriate grounding wire, connect the ground
terminal to the chassis ground connection.
4
3
2
1
RUGGEDCOM RX1536
Installation Manual, 04/2021, C79000-G8976-1488-02